AMPS VOLTS DETERMINATION DEFINE AMPS VOLTS WATTS VISUALLY DETERMINE AMPS & VOLTS VOLTAGE at the SEC VOLTAGE by EQUIPMENT LIMITING FACTOR sets AMPS SE CABLE SIZES vs AMPS UNDERGROUND SERVICE LATERALS ALUMINUM SECs & WIRING MAIN DISCONNECT AMPACITY PANEL AMPACITY ELECTRIC METERS & METER BASES AMPACITY - the LIMITING FACTOR Article Reviewers More Information InspectAPedia TM Home & Site Map Air Conditioning InspectAPedia Bookstore Electrical Environment Exteriors Heating Home Inspection Insulate Ventilate Interiors Mold Inspect/Test Plumbing Water Septic Roofing Structure Accuracy & Bias Pledge Contact Us |
This article explains how to estimate the electrical service size, (or "electrical power" or "service amps") at a building by visual examination of the service entry cables, electric meter and meter base, electrical service panel, main switch, and other details. Visual inspection and use of digital multimeters(DMMs), Volt-ohm meters (VOMs), neon testers, and electrical inspection safety are discussed. Photographs and sketches illustrate electrical panels, meter bases, and electric meters. One of the most frequently asked questions at ASHI Education Seminars and Conferences is "How do I determine the service amperage?" Readers of this article should also be sure to review Safety Hazards and Safe Electrical Inspection Procedures for examining Residential Electrical Panels. © Copyright 2008 Daniel Friedman, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use links at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website. LIMITING FACTOR sets AMPS - Checking the Electrical Service amperage - what is the limiting factorThe safe and proper service amperage available at a property is set by the smallest of: the service conductors, the main disconnect fuse or switch, or the rated capacity of the electric panel itself. The inspector should consider all three of these and report any inconsistencies among them. The main fuse/ circuit breaker (CB) is the only component which actively limits amperage at a property by shutting off loads drawing more than the main fuse rating. (Undersized conductors or service panels, if switched by a mismatched and oversized fuse or breaker, will permit more current to flow than their design intended, and can then overheat causing a risk of fire.) The main breakers or fuses are permitted to be smaller (have lower overcurrent protection) than the capability of the service equipment (panel) and conductors (entrance cable). For example, a 2AWG copper service conductor (rated for 125 Amps, or in Canada for 120 Amps) to a panel using a 100-Amp main (service disconnect) is not a defect.["Residential Electrical Inspection," Douglas Hansen, ITA class material, Ver. 6.1 Oct. 1991, Los Altos, CA] You may want to point out to your client that such a service can be upgraded to higher amperage simply by installing larger main fuses/breakers. Note that the main disconnect may be a fuse, breaker, or switch which is physically separate from the distribution panel. This is more common in older equipment installations and in very large commercial high-amperage installations. common defect found in upgrades of older equipment is the installation of a new 100-Amp panel and main breaker while failing to replace the old 60-amp service entry cables. This is either incomplete work or work by an untrained person. Keep in mind that by service entry cables we're referring to the cables from the mast head (point of attachment of overhead wires to the building) down to the meter and from meter into the main switch or panel. Overhead wires, being cooled by open air, may be of a smaller diameter determined to be safe by the utility company for open air use. Electrical Services providing less than 100 Amps are found in older properties but for a detached single-family dwelling these are considered obsolete and are a financing issue with some US lenders.[NOTE: NEC-230-42(b,1) and some FHA, VA, and private Banks in some states.] Services of 60 Amp capacity are still allowed in at least some Canadian areas and in the US for loads such as individual apartments. Inspectors should not write up 60-Amp services as a defect without first checking these points. In cabins or similar vacation structures in the U.S. and Canada, and in buildings in some other countries such as Mexico, much smaller amperage services are often brought into the building. Home Inspectors should make clear to all parties that generally, electrical defects are unsafe conditions, can be quite dangerous, and deserve prompt attention. One exception: an undersized service, if it is properly fused, will be inconvenient but is not itself inherently unsafe. For such systems the safety and fire risks come more often from the temptation of frustrated owners to subvert or bypass the safety devices the classic "penny in the fuse base" problem. Use links at the left of each page or the links given just below to navigate this document or to view other topics at this website. Green links show where you are in our document or website. AMPS VOLTS DETERMINATION DEFINE AMPS VOLTS WATTS VISUALLY DETERMINE AMPS & VOLTS VOLTAGE at the SEC VOLTAGE by EQUIPMENT LIMITING FACTOR sets AMPS SE CABLE SIZES vs AMPS UNDERGROUND SERVICE LATERALS ALUMINUM SECs & WIRING MAIN DISCONNECT AMPACITY PANEL AMPACITY ELECTRIC METERS & METER BASES ELECTRIC METER BASES ELECTRIC METERS INSPECTING METERS & BASES AMPACITY - the LIMITING FACTOR Technical ReviewersParticular thanks are due to experts and also consumers who read these articles and suggest corrections, changes, and additions to the material. Content suggestions, technical corrections and content critique are invited for any of the content at our website.
Use links at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website. More expert information on Inspecting Electrical Equipment and Electrical Safety for Inspectors | |
|
AMPS VOLTS DETERMINATION DEFINE AMPS VOLTS WATTS VISUALLY DETERMINE AMPS & VOLTS VOLTAGE at the SEC VOLTAGE by EQUIPMENT LIMITING FACTOR sets AMPS SE CABLE SIZES vs AMPS UNDERGROUND SERVICE LATERALS ALUMINUM SECs & WIRING MAIN DISCONNECT AMPACITY PANEL AMPACITY ELECTRIC METERS & METER BASES AMPACITY - the LIMITING FACTOR More Information InspectAPedia TM Home & Site Map Air Conditioning InspectAPedia Bookstore Electrical Environment Exteriors Heating Home Inspection Insulate Ventilate Interiors Mold Inspect/Test Plumbing Water Septic Roofing Structure Accuracy & Bias Pledge Contact Us |
More Information on Electrical Inspections & Building Diagnostic Inspections and Repairs
|
10/21/2007 - 1/16/1993 www.inspect-ny.com/electric/ElecAmps3.htm - Web page design & content © 2007-1993 Copyright Daniel Friedman All Rights Reserved