InspectAPedia TM

Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice
InspectAPedia
Home
| Air
Conditioning
| Electrical | Environment | Exteriors | Heating | Home
Inspection
| Insulate
Ventilate
| Interiors | Mold
Inspect/Test
| Plumbing
Water
Septic
| Roofing | Structure | Contact Us
New Directory of Professionals to Inspect or Test a Building New


ELECRICAL PANEL INSPECTION
COURSE SUMMARY
ELECTRICAL INSPECTION SAFETY
ELECTRICAL VOCABULARY
SERVICE DROP
  WIRE CLEARANCES
SERVICE ENTRY WIRING
DETERMINE SERVICE AMPACITY
  TABLE OF SERVICE AMPACITY
  SERVICE AMPACITY DEFECTS
ELECTRIC SERVICE GROUNDING
  TABLE OF GROUND WIRE SIZES
  SERVICE GROUNDING
MAIN DISCONNECT
  MAIN SWITCH LOCATION
  MAIN SWITCH
SYSTEM GROUNDING
DISTRIBUTION PANELS
  PANEL COVER
  CIRCUIT WIRING AMPS FUSING
  PROBLEM-BRAND ELEC PANELS
  ELEC PANEL LOCATION
  FUSES vs CIRCUIT BREAKERS
  MAIN DISCONNECT INSPECTION
  OTHER PANEL DEFECTS
  PANEL FUSING/BREAKER
  PANEL WIRING
More Information

InspectAPedia TM Home & Site Map
Air Conditioning
InspectAPedia Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Bias Pledge
Contact Us




Photograph of  this FPE electric panel with several safety concerns

How to Inspect Residential Electrical Panels
ElectricAPedia ©

Google
 
  • Class on how to inspect electrical panels
  • Home inspection procedures and safety
This document discusses procedures for safe and effective visual inspection of residential electrical panels by trained building inspection professionals, home inspectors, electrical inspectors, and electricians. It was presented by Daniel Friedman - www.inspect-ny.com, at the Hudson Valley chapter of the American Society of Home Inspectors - HVASHI Seminar 12 Sept 2002, Updated April 2006. Readers of this article should also be sure to review Safety Hazards and Safe Electrical Inspection Procedures for Inspectors examining Residential Electrical Panels.

© Copyright 2008 Daniel Friedman, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use the links at page left to navigate this document or to go to Other Website Topics. Green links at left show where you are in our document & website.

Our site offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at inspect-ny.com/appointment.htm.

COURSE SUMMARY - Electric Panel Inspection Course Summary

SAFETY WARNING: Inspection of electrical systems risks death by fatal electrical shock. The procedures discussed in this class require that the cover of the panel be removed in order to expose the panel interior. Homeowners should not attempt this step, and no one lacking proper electrical safety training should remove the electrical panel cover nor attempt to perform the tasks discussed in this class. ELECTRICAL CODE COMPLIANCE WARNING: these inspection procedures are designed to assist in the detection and reporting of electrical service defects which can be recognized by visual inspection. This inspection is not for the purpose of determining compliance with local or national electrical codes. Guidelines given here, such as overhead wire clearances, are based on widely-accepted codes and standards, but local building codes may specify other or different restrictions.

Part I - Electrical Panel Defect Identification - Principles

  • Safety Procedures for Electrical Inspectors
  • Electrical Power Delivery System
  • Common Electrical Panel and Wiring Defects

Part II - Electrical Panel Defect Recognition - Photos of Electrical Defects & Examples

This section of the class contains annotated field photographs of certain electrical panel defects which can be recognized by visual inspection. That is, no instruments, no measurements, and no insertion of any device into the electrical panel are required to perform these tasks. I have these photos on file and will add them to this presentation if readers request.


ELECRICAL PANEL INSPECTION
COURSE SUMMARY
ELECTRICAL INSPECTION SAFETY
ELECTRICAL VOCABULARY
SERVICE DROP
SERVICE ENTRY WIRING
DETERMINE SERVICE AMPACITY
ELECTRIC SERVICE GROUNDING
MAIN DISCONNECT
SYSTEM GROUNDING
DISTRIBUTION PANELS
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

ELECTRICAL INSPECTION SAFETY - Overview of the Residential Electrical System and Electrical Inspection Hazards

  • The Electrical System Function is to power home systems/appliances, providing safe distribution of electrical power throughout the building.
  • Costs: operation, repair, updating/expansion

Safety Procedures for Residential Building Electrical Inspectors

SAFETY WARNING: Inspection of electrical systems risks death by fatal electrical shock. The procedures discussed in this class require that the cover of the panel be removed in order to expose the panel interior. Homeowners should not attempt this step, and no one lacking proper electrical safety training should remove the electrical panel cover nor attempt to perform the tasks discussed in this class.

Electrical Panel Inspection Safety - Critical Warnings

Do not:

  • touch SEC or other wires
  • insert probes/tools into panel
  • remove suspect panel covers (more later)
  • touch electrical equipment from unsafe location (wet, off balance, grounded, etc.)

Protect nearby observers, clients, etc. from hazards [added by DF 2/13/2006]

  • Do not permit observers to touch the inspector while that person is working on or at the electrical panel.
  • Do not permit observers to touch the electrical panel nor to insert any tool, pencil, or other object into the panel.
  • The inspector should stand with his/her body between observers and the panel, and should be prepared to physically block an attempt by the observer to reach towards or touch the electrical panel while its cover has been removed.
  • Explain, calmly and without exaggeration, but accurately, the shock and fire hazards to observers and instruct the observers on what to do if the inspector him/herself is being shocked by the panel. [Don't touch the person being shocked. If a wooden board or stake is nearby, one might attempt to push the inspector away from the panel using that device or to turn off the main breaker or fuse. Call for help immediately.

More Reading on Electrical Inspection Safety


Electrical inspectors planning to examine residential electrical panels, in addition to obtaining proper training, should read the following:


ELECRICAL PANEL INSPECTION
COURSE SUMMARY
ELECTRICAL INSPECTION SAFETY
ELECTRICAL VOCABULARY
SERVICE DROP
SERVICE ENTRY WIRING
DETERMINE SERVICE AMPACITY
ELECTRIC SERVICE GROUNDING
MAIN DISCONNECT
SYSTEM GROUNDING
DISTRIBUTION PANELS
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

Electrical Vocabulary for Residential Electrical Inspectors

  • Service Drop/Service Laterals (overhead/underground from street) - Insp. not required; [note clearance/tree/condition/number of wires]
  • Service Entrance (masthead, service entrance conductors, meter/meter)
  • Service Voltage
  • Service Amperage
  • Service Equipment
  • Service disconnect - main overcurrent dev.
  • Service box, main panel, service panel
  • Grounding equipment - rod/electrode, grounding conductor
  • Grounding wire: the "ground wire," normally inactive, alternative path from various devices to ground, exercised in abnormal conditions to permit fuse to blow and reduce shock hazard
  • Grounded wire: neutral wire, normally carries return current, in daily use, gives flow path of current from source to earth
  • Grounding electrode conductor: "the ground wire" from service equipment to ground at water pipe or electrode(s)
  • Equipment grounding conductors: "ground wires" on each branch circuit throughout the house
  • Grounding: connect something to earth (0 potential)
  • Bonding: joining two electrical conductors so will be at same electrical potential (FYI: gas piping not used for grounding, is bonded to the grounding system)

ELECRICAL PANEL INSPECTION
COURSE SUMMARY
ELECTRICAL INSPECTION SAFETY
ELECTRICAL VOCABULARY
SERVICE DROP
SERVICE ENTRY WIRING
DETERMINE SERVICE AMPACITY
ELECTRIC SERVICE GROUNDING
MAIN DISCONNECT
SYSTEM GROUNDING
DISTRIBUTION PANELS
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

Inspecting the Electrical Service Drop or Service Lateral bringing electrical power to a building

  • Lateral - underground (mostly not visible)
    Look For: settlement, conduit damage ?
  • Drop - overhead
    Look For: number of wires -2/120V, 3/240V, 4/3-phase
    Look For: drip loop - present?
    Look For: service cap - secure, facing down, present?
    Look For: service mast - secure, straight, flashed, present? Lateral - underground (mostly not visible)
    Look For: settlement, conduit damage ?

Electrical Service Drop Wire Clearances and Other Defects

  • roadway 18 ft. overhead
  • driveway 12 ft. overhead
  • flat roof 8-10 ft. overhead
  • roof 18" at mast, 3 ft. passing over
  • walkway 10 ft. overhead
  • swim pool 18 ft. vertical clearance, 10 ft. horizontal clearance
  • not over 30 ft. above grade
  • less than 3 ft. from windows, fire escapes, doors
  • damaged, frayed
  • trees, vines
  • well-secured to house
  • well-connected to service entrance cable (SEC)

ELECRICAL PANEL INSPECTION
COURSE SUMMARY
ELECTRICAL INSPECTION SAFETY
ELECTRICAL VOCABULARY
SERVICE DROP
SERVICE ENTRY WIRING
DETERMINE SERVICE AMPACITY
ELECTRIC SERVICE GROUNDING
MAIN DISCONNECT
SYSTEM GROUNDING
DISTRIBUTION PANELS
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

Inspecting the Electrical Service Entry Wiring bringing electrical power to the electric meter

  • Mast, conduit, cable: weather tight
  • service cap
  • roof flashing
  • conduit required at roof penetrations
  • conduit joints
  • top and base of meter
  • at wall penetration
  • well connected to service entrance cable (SEC)
frayed SEC cables, abandoned SEC cables

A study by the author (Reporting Extent and Sources of Rust and Corrosion in Electrical Panels, HOLM Conference) showed that very common sources of water leaks into and damaging electrical panels include frayed SEC, leaks at the top of the meter, and leaks at the building wall where the SEC passes from the bottom of a meter pan into the building electrical panel.


ELECRICAL PANEL INSPECTION
COURSE SUMMARY
ELECTRICAL INSPECTION SAFETY
ELECTRICAL VOCABULARY
SERVICE DROP
SERVICE ENTRY WIRING
DETERMINE SERVICE AMPACITY
  TABLE OF SERVICE AMPACITY
  SERVICE AMPACITY DEFECTS
ELECTRIC SERVICE GROUNDING
MAIN DISCONNECT
SYSTEM GROUNDING
DISTRIBUTION PANELS
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

How to Determine Residential Electrical Service Ampacity

Do not rely on the ampacity printed on the main fuse or breaker, though that information is important. Examine the following:

  • service drop wire size
  • mast diameter
  • 1-inch 60A mast
  • 2-inch 200A lateral
  • meter base size
  • meter rating
  • service box rating
  • distribution panel rating
  • total of all fuses or breakers in panel (the sum is NOT the service ampacity as % utilization applies)

So what determines the actual service ampacity at a building?

  • Smallest link in the chain determines
  • Best indication is size of SEC + id CU/AL
  • IF SEC is not visible, look at service disconnect
  • Specify if unable to determine, and why

ELECRICAL PANEL INSPECTION
COURSE SUMMARY
ELECTRICAL INSPECTION SAFETY
ELECTRICAL VOCABULARY
SERVICE DROP
SERVICE ENTRY WIRING
DETERMINE SERVICE AMPACITY
  Table of Service Ampacity
  SERVICE AMPACITY DEFECTS
ELECTRIC SERVICE GROUNDING
MAIN DISCONNECT
SYSTEM GROUNDING
DISTRIBUTION PANELS
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

A General Table of Electrical Service Ampacity vs. Service Entry Cable Sizes

AMPSCopperAluminum
3010*8*
606*6*
706*4*
10042
12521/0
1501/02/0
2002/04/0

More Reading:
Ampacity of an Electrical Service - Details of how to determine electrical service ampacity and voltage by visual inspection and/or safe use of test instruments.


ELECRICAL PANEL INSPECTION
COURSE SUMMARY
ELECTRICAL INSPECTION SAFETY
ELECTRICAL VOCABULARY
SERVICE DROP
SERVICE ENTRY WIRING
DETERMINE SERVICE AMPACITY
  TABLE OF SERVICE AMPACITY
  Service Ampacity Defects
ELECTRIC SERVICE GROUNDING
MAIN DISCONNECT
SYSTEM GROUNDING
DISTRIBUTION PANELS
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

Electrical Service Ampacity Defects

  • inadequate / marginal total capacity for the modern use of the building. Some lenders require a minimum of 100A.
  • Some utility companies will not replace an old 60A service (and meter) and will require that service be upgraded.
  • load calculation of required service ampacity for buildings is not required during a home inspection but the inspector should be familiar with that procedure

ELECRICAL PANEL INSPECTION
COURSE SUMMARY
ELECTRICAL INSPECTION SAFETY
ELECTRICAL VOCABULARY
SERVICE DROP
SERVICE ENTRY WIRING
DETERMINE SERVICE AMPACITY
ELECTRIC SERVICE GROUNDING
  TABLE OF GROUND WIRE SIZES
  SERVICE GROUNDING
MAIN DISCONNECT
SYSTEM GROUNDING
DISTRIBUTION PANELS
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

Inspecting Electrical Service Grounding Equipment

  • Required for safety, lets fuses blow
  • Example: toaster falls into metal sink
  • Grounding Electrode Conductor wire from service equipment to
  • house plumbing (grounds the plumbing)
  • Entering metal water pipe (grounds the system)
  • Grounding Electrode (two now recommended)
  • Continuous, no splices, meter bypass
  • Copper
  • Aluminum - insulated solid conductor
  • Aluminum - insulated multi-strand
  • Aluminum - bare vs. insulated (risk of corrosion, break in wire, loss of safe grounding)

Table of Electrical Ground Wire Sizes

Ground Gauge CU (Copper) Service Size
#8 to 100A
#6 to 125A
#4 to 165A 4*
#3 to 200A

Electrical Service Grounding Defects & Conditions

  • not found in sub panel feeder
  • attached to plastic pipe
  • attached to abandoned pipe
  • spliced
  • loose or missing connections
  • inaccessible connections
  • no meter bypass
  • not found in main box
  • not found in sub panel feeder
  • attached to plastic pipe
  • attached to abandoned pipe
  • spliced
  • loose or missing connections
  • inaccessible connections
  • no water meter/water shutoff valve bypass
  • neutral bonded to ground downstream of box (or upstream)
  • neutral not bonded to ground at box
  • main panel not bonded to ground wire
  • undersized ground wire
  • ground rod cut off or short
  • corroded ground wire
  • bare aluminum exposed to corrosion
  • neutral. bonded downstream of box (or upstream)
  • neutral. not bonded to ground at box
  • main panel not bonded to ground wire
  • undersized ground wire
  • ground rod cut off or short
  • corroded ground wire
  • bare aluminum exposed to corrosion

ELECRICAL PANEL INSPECTION
COURSE SUMMARY
ELECTRICAL INSPECTION SAFETY
ELECTRICAL VOCABULARY
SERVICE DROP
SERVICE ENTRY WIRING
DETERMINE SERVICE AMPACITY
ELECTRIC SERVICE GROUNDING
MAIN DISCONNECT
  MAIN SWITCH LOCATION
  MAIN SWITCH
SYSTEM GROUNDING
DISTRIBUTION PANELS
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

Inspecting the Residential Electrical Main Disconnect Panel or "Box" for Defects

  • Main control center for house
  • Integrated or separate service disconnect (main breaker or fuses) - need main disconnect if more than 6 switches

Electrical Service Box Location Defects

  • OK indoors our outside (if weather tight)
  • NOT OK bathroom, clothes closet, kitchen cabinets
  • Should Be at eye level, easily accessible, with 3 ft. working clearance

Inspecting the Electric Service Panel for Condition Defects

The Implications: electrical shock or fire

  • Poor access, not secured
  • Rust, corrosion
  • Overheating
  • Over fusing or box rating too small
  • Inappropriate. mounting surface / not secure
  • Damaged parts
  • Poor connections, poor wiring
  • Illegal taps
  • Neutral wire defects
  • fused, bypasses box, fused upstream
  • Obsolete
  • Exterior, not weather tight
  • Specific Electrical Panel Product Defects, see below

ELECRICAL PANEL INSPECTION
COURSE SUMMARY
ELECTRICAL INSPECTION SAFETY
ELECTRICAL VOCABULARY
SERVICE DROP
SERVICE ENTRY WIRING
DETERMINE SERVICE AMPACITY
ELECTRIC SERVICE GROUNDING
MAIN DISCONNECT
SYSTEM GROUNDING
DISTRIBUTION PANELS
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

SYSTEM GROUNDING - Inspecting Residential Electrical System Grounding for Defects

  • This wiring is for Emergency-use only - it should never be wired so as to carry current during normal operation. (E.g. This occurs if a sub panel bonds the neutral to ground wires).
  • Provides better path for current than a person, blows fuse/breaker, dissipates static, may dissipate lightning
  • Example: loose black in metal box touches side; current flows through person when touched, depends on who is grounded

ELECRICAL PANEL INSPECTION
COURSE SUMMARY
ELECTRICAL INSPECTION SAFETY
ELECTRICAL VOCABULARY
SERVICE DROP
SERVICE ENTRY WIRING
DETERMINE SERVICE AMPACITY
ELECTRIC SERVICE GROUNDING
MAIN DISCONNECT
SYSTEM GROUNDING
DISTRIBUTION PANELS
  PANEL COVER
  CIRCUIT WIRING AMPS FUSING
  PROBLEM-BRAND ELEC PANELS
  ELEC PANEL LOCATION
  FUSES vs CIRCUIT BREAKERS
  MAIN DISCONNECT INSPECTION
  OTHER PANEL DEFECTS
  PANEL FUSING/BREAKER
  PANEL WIRING
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

DISTRIBUTION PANELS - Inspecting Residential Electrical Distribution Panels for Defects

  • Main and sub panels, aka "service panels, aux panels, sub panels, fuse boxes, fuse box"
  • Fed from meter to main breaker/fuse or fed from separate service connect
  • distributes electricity through house branch circuits and special (range etc) circuits
  • each sub circuit must be protected (fuse/breaker)

PANEL COVER - Residential Electrical Panel Cover Inspection and Special Safety Hazards - Look before you touch!

  • Look (and test?) before touching, open door, look again (rust, burns, gaps, unsafe stance)
  • Block client from touching equipment
  • May be unsafe to remove upper cover of combination panels (service main at top)
  • Sheet metal screw shorts, shocks, fires
  • Swing-out covers can pinch wires

ELECRICAL PANEL INSPECTION
COURSE SUMMARY
ELECTRICAL INSPECTION SAFETY
ELECTRICAL VOCABULARY
SERVICE DROP
SERVICE ENTRY WIRING
DETERMINE SERVICE AMPACITY
ELECTRIC SERVICE GROUNDING
MAIN DISCONNECT
SYSTEM GROUNDING
DISTRIBUTION PANELS
  PANEL COVER
  CIRCUIT WIRING AMPS FUSING
  PROBLEM-BRAND ELEC PANELS
  ELEC PANEL LOCATION
  FUSES vs CIRCUIT BREAKERS
  MAIN DISCONNECT INSPECTION
  OTHER PANEL DEFECTS
  PANEL FUSING/BREAKER
  PANEL WIRING
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

CIRCUIT WIRING AMPS FUSING - Electrical branch circuit wiring amps/fusing defects - Copper electrical wiring

Match wiring gauge to ampacity:

  • 14 gauge - 15Amps
  • 12 gauge - 20 Amps
  • 10 gauge - 30 Amps
  • 8 gauge - 40 Amps
  • Aluminum: 1 size larger, currently only multi-strand on single-use circuits like range /DHW/AC older solid conductor AL may be present in next gauge. (Solid conductor aluminum branch circuit wiring is unsafe, a fire hazard, and requires repair - see The Aluminum Wiring Website

PROBLEM-BRAND ELEC PANELS - Problem-Brand Electrical Panels


ELECRICAL PANEL INSPECTION
COURSE SUMMARY
ELECTRICAL INSPECTION SAFETY
ELECTRICAL VOCABULARY
SERVICE DROP
SERVICE ENTRY WIRING
DETERMINE SERVICE AMPACITY
ELECTRIC SERVICE GROUNDING
MAIN DISCONNECT
SYSTEM GROUNDING
DISTRIBUTION PANELS
  PANEL COVER
  CIRCUIT WIRING AMPS FUSING
  PROBLEM-BRAND ELEC PANELS
  ELEC PANEL LOCATION
  FUSES vs CIRCUIT BREAKERS
  MAIN DISCONNECT INSPECTION
  OTHER PANEL DEFECTS
  PANEL FUSING/BREAKER
  PANEL WIRING
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

ELEC PANEL LOCATION - Electrical Panel Location Defects

  • Mains: Not in: bathroom, clothes closet, kitchen cabinets, stairwells (same as service disconnect)
  • Should be at eye level, easily accessible, 3 ft. clearance
  • Subs: may be located almost anywhere (still some Sub panels are improper as above).
  • Finding hidden sub panels: Look for feeder-breaker/fuse or wires leaving main

FUSES vs CIRCUIT BREAKERS - Relative Electrical Safety of Fuses versus Circuit Breakers

  • Fuses more reliable to "blow" - not mechanical BUT easier to over-fuse (reduce with S-type retro)
  • Breakers more convenient to reset can be tested without having to then replace the safety device - less likely to be over-fused (but over fusing still happens - compare wire gauge to breaker ampacity)

ELECRICAL PANEL INSPECTION
COURSE SUMMARY
ELECTRICAL INSPECTION SAFETY
ELECTRICAL VOCABULARY
SERVICE DROP
SERVICE ENTRY WIRING
DETERMINE SERVICE AMPACITY
ELECTRIC SERVICE GROUNDING
MAIN DISCONNECT
SYSTEM GROUNDING
DISTRIBUTION PANELS
  PANEL COVER
  CIRCUIT WIRING AMPS FUSING
  PROBLEM-BRAND ELEC PANELS
  ELEC PANEL LOCATION
  FUSES vs CIRCUIT BREAKERS
  MAIN DISCONNECT INSPECTION
  OTHER PANEL DEFECTS
  PANEL FUSING/BREAKER
  PANEL WIRING
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

MAIN DISCONNECT INSPECTION - Electrical Panel Main Disconnect Inspection - Do you Pull the Main Fuse or Test the Main Breaker?

  • may be necessary to get some panel covers off
  • may be unsafe or may not want to shut power off to building
  • ask occupant/owner before killing power
  • report limitations to inspection
  • re-set accidentally-tripped breakers and leave note

OTHER PANEL DEFECTS - Other Electrical Panel Defects Discoverable by Visual Inspection

  • Obsolete and/or fused neutrals
  • Damaged panel/components
  • Loose panel
  • Inappropriate support material
  • Unprotected panel openings/knockouts
  • Undersized panel - physical size/crowded
  • Overheating - look at mains, breakers, bus, neutrals, wires
  • Rust or water - look for rust, corrosion, overheating, subtle spots, suspect hidden damage to bus or breakers, look for water trace marks on entering SEC
  • circuits not labeled
  • panel overcrowded
  • poor access to panel
  • panel upside down or switches "on" in down position (obsolete)
  • Panel used-with and not suitable for AL wiring

ELECRICAL PANEL INSPECTION
COURSE SUMMARY
ELECTRICAL INSPECTION SAFETY
ELECTRICAL VOCABULARY
SERVICE DROP
SERVICE ENTRY WIRING
DETERMINE SERVICE AMPACITY
ELECTRIC SERVICE GROUNDING
MAIN DISCONNECT
SYSTEM GROUNDING
DISTRIBUTION PANELS
  PANEL COVER
  CIRCUIT WIRING AMPS FUSING
  PROBLEM-BRAND ELEC PANELS
  ELEC PANEL LOCATION
  FUSES vs CIRCUIT BREAKERS
  MAIN DISCONNECT INSPECTION
  OTHER PANEL DEFECTS
  PANEL FUSING/BREAKER
  PANEL WIRING
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

PANEL FUSING/BREAKER - Electric Panel Fusing/Breaker Defects

PANEL WIRING - Electric Panel Wiring Condition Defects

  • sheathing not removed
  • overheating
  • loose
  • damaged
  • not secured
  • wire crosses bus bars
  • abandoned wires in panel
Building,home,inspection,environmental,inspect,test,testing,investigation,home inspection,ASHI,American Society of Home Inspectors Air,C)trap Daniel Friedman,environmental inspection,environmental testing,diagnosis,repair,prevention,leak,damage, litigation,lawsuit,lawyer,legal,expert witness,testimony,forensic,engineering,fire,hygienist,industrial,

More expert information on this topic

Reference sources for this Electrical Panel Inspection Class

  • * Safety Hazards and Safe Inspection Procedures for Electrical and Home Inspectors at Residential Electric Panels
  • Aluminum Wiring Information Website Aluminum Electrical Wiring Hazards and Repairs: in-depth authoritative info, photos, documents including selection of proper vs. ineffective repair methods. E.g.: Ideal 65 "Twister" purple connector fails in field and lab testing with aluminum wire.
  • Ampacity of an Electrical Service: How to determine the electrical service size or ampacity entering a building
  • Circuit Breaker, a bad one fails to trip failure at aluminum bus-to-circuit breaker connection - field report and photographs
  • Electrical Panels, How to Inspect in Buildings, safety for electrical inspectors, electrical panel, fusing, wiring defects, defective products. Inspection Class Presentation
  • Federal Pacific Electric (FPE) Stab-Lok Circuit Breaker Panel Hazards Website - Latent fire hazards, in-depth authoritative research, documents, advice on Stab-Lok electric panel and circuit breaker failures and what to do when this equipment is found in buildings.
  • Lightning Strike Risk Assessment, Protection Systems & Services
  • Multi-wire branch circuit inspection and defects
  • Zinsco Electrical Circuit Breaker Failures: overheating, failure to trip, burn-ups involving Zinsco and certain Sylvania electrical panel components - page under development March 2006.
  • "Electrical System Inspection Basics," Richard C. Wolcott, ASHI 8th Annual Education Conference, Boston 1985.
  • "Simplified Electrical Wiring," Sears, Roebuck and Co., 15705 (F5428) Rev. 4-77 1977 [Lots of sketches of older-type service panels.]
  • "How to plan and install electric wiring for homes, farms, garages, shops," Montgomery Ward Co., 83-850.
  • "Electrical System Inspection Basics," Richard C. Wolcott, ASHI 8th Annual Education Conference, Boston 1985.
  • "Simplified Electrical Wiring," Sears, Roebuck and Co., 15705 (F5428) Rev. 4-77 1977 [Lots of sketches of older-type service panels.]
  • "How to plan and install electric wiring for homes, farms, garages, shops," Montgomery Ward Co., 83-850.
  • "Home Wiring Inspection," Roswell W. Ard, Rodale's New Shelter, July/August, 1985 p. 35-40.
  • "Evaluating Wiring in Older Minnesota Homes," Agricultural Extension Service, University of Minnesota, St. Paul, Minnesota 55108.
  • "Electrical Systems," A Training Manual for Home Inspectors, Alfred L. Alk, American Society of Home Inspectors (ASHI), 1987, available from ASHI. [DF NOTE: I do NOT recommend this obsolete publication, though it was cited in the original Journal article as it contains unsafe inaccuracies]
  • "Basic Housing Inspection," US DHEW, S352.75 U48, p.144, out of print, but is available in most state libraries.
  • Rust and Corrosion in Electrical Panels, A Study and Report on Frequency and Cause for Electrical and Home Inspectors at Residential Electric Panels

  • Directory of Home Inspectors accessible via internet
  • Electrical System & Wiring Hazard Inspection, Detection, Cause, Remedy, Prevention - Main Electrical Page

More expert information on this topic



ELECRICAL PANEL INSPECTION
COURSE SUMMARY
ELECTRICAL INSPECTION SAFETY
ELECTRICAL VOCABULARY
SERVICE DROP
SERVICE ENTRY WIRING
DETERMINE SERVICE AMPACITY
ELECTRIC SERVICE GROUNDING
MAIN DISCONNECT
SYSTEM GROUNDING
DISTRIBUTION PANELS
More Information

InspectAPedia TM Home & Site Map
Air Conditioning
InspectAPedia Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Bias Pledge
Contact Us

More Information on Electrical Inspections, Building Diagnostic Inspections and Repairs

  • * Safety Hazards and Safe Inspection Procedures for Electrical and Home Inspectors at Residential Electric Panels
  • Aluminum Wiring Information Website Aluminum Electrical Wiring Hazards and Repairs: in-depth authoritative info, photos, documents including selection of proper vs. ineffective repair methods. E.g.: Ideal 65 "Twister" purple connector fails in field and lab testing with aluminum wire.
  • Ampacity of an Electrical Service: How to determine the electrical service size or ampacity entering a building
  • Circuit Breaker, a bad one fails to trip failure at aluminum bus-to-circuit breaker connection - field report and photographs
  • Electrical Panels, How to Inspect in Buildings, safety for electrical inspectors, electrical panel, fusing, wiring defects, defective products. Inspection Class Presentation
  • Federal Pacific Electric (FPE) Stab-Lok Circuit Breaker Panel Hazards Website - Latent fire hazards, in-depth authoritative research, documents, advice on Stab-Lok electric panel and circuit breaker failures and what to do when this equipment is found in buildings.
  • Lightning Strike Risk Assessment, Protection Systems & Services
  • Multi-wire branch circuit inspection and defects
  • Zinsco Electrical Circuit Breaker Failures: overheating, failure to trip, burn-ups involving Zinsco and certain Sylvania electrical panel components - page under development March 2006.
  • "Electrical System Inspection Basics," Richard C. Wolcott, ASHI 8th Annual Education Conference, Boston 1985.
  • "Simplified Electrical Wiring," Sears, Roebuck and Co., 15705 (F5428) Rev. 4-77 1977 [Lots of sketches of older-type service panels.]
  • "How to plan and install electric wiring for homes, farms, garages, shops," Montgomery Ward Co., 83-850.
  • "Electrical System Inspection Basics," Richard C. Wolcott, ASHI 8th Annual Education Conference, Boston 1985.
  • "Simplified Electrical Wiring," Sears, Roebuck and Co., 15705 (F5428) Rev. 4-77 1977 [Lots of sketches of older-type service panels.]
  • "How to plan and install electric wiring for homes, farms, garages, shops," Montgomery Ward Co., 83-850.
  • "Home Wiring Inspection," Roswell W. Ard, Rodale's New Shelter, July/August, 1985 p. 35-40.
  • "Evaluating Wiring in Older Minnesota Homes," Agricultural Extension Service, University of Minnesota, St. Paul, Minnesota 55108.
  • "Electrical Systems," A Training Manual for Home Inspectors, Alfred L. Alk, American Society of Home Inspectors (ASHI), 1987, available from ASHI. [DF NOTE: I do NOT recommend this obsolete publication, though it was cited in the original Journal article as it contains unsafe inaccuracies]
  • "Basic Housing Inspection," US DHEW, S352.75 U48, p.144, out of print, but is available in most state libraries.
  • Rust and Corrosion in Electrical Panels, A Study and Report on Frequency and Cause for Electrical and Home Inspectors at Residential Electric Panels

  • Directory of Home Inspectors accessible via internet
  • Electrical System & Wiring Hazard Inspection, Detection, Cause, Remedy, Prevention - Main Electrical Page

goto InspectAPedia.com - authoritative, in-depth Building Diagnostic and Repair Information for building buyers, owners, inspectorsInspectAPedia TM Home & Site Map - Building Inspection, Diagnosis, & Repair, Environmental Inspection & Testing - Research Website

GO TO the MOLD and INDOOR ENVIRONMENT INFORMATION CENTER for in-depth advice on avoiding testing for or cleaning up mold and other indoor environmental hazards, odors, gases, contaminantsThe Mold Information Center: What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems

GO TO our PRE PURCHASE BUILDING INSPECTION SERVICES: Authoritative information for home buyers and home owners is included with your inspection.Home Inspection Construction Consulting Services & advice for home buyers

GO TO MOLD TEST KITS: This expert-recommended mold test kit is cheap and yet top performing *IF* you use a competent analysis laboratory!Use this simple, economical mold test kit by following our instructions on how to collect and mail mold samples to our lab

GO TO IAQ/MOLD-TEST LAB SERVICES: Mold, Pollen, indoor air quality, field and laboratory services by an expert.Environmental Inspection, Testing, & Diagnosis On-Site IAQ, Gas, Air Testing, Mold Investigation, Sick Building Diagnosis, Lab Services, & Remediation Plan Preparation - indoor air quality testing, problem source determination, supporting lab work, written remediation plan addressing removal of environmental and other hazards and prevention of their recurrence.

CONTACT Daniel Friedman - Dan is a senior ASHI home inspector, nationally recognized expert on building inspection, building failures, and sick building investigationContact Daniel Friedman for website content suggestions or for fee-paid consulting

Google
 
Advertise on This Website →

03/29/2007 - www.inspect-ny.com/electric/ElecPanelInsp.htm - © 2006-2002 Copyright Daniel Friedman All Rights Reserved