ELECTRICAL INSPECTION, DIAGNOSIS, REPAIR AFCIs ARC FAULT CIRCUIT INTERRUPTERS ALUMINUM SECs & WIRING ALUMINUM WIRING HAZARDS AMPS & VOLTS DETERMINATION AMPACITY - the LIMITING FACTOR BOOKSTORE - ELECTRICAL CIRCUIT BREAKER FAILURE Classified CIRCUIT BREAKER WARNING DEFINITIONS of ELECTRICAL TERMS DIRECTORY OF ELECTRICIANS ELECTRIC METERS & METER BASES AMPACITY - the LIMITING FACTOR ELECTRIC PANEL AMPACITY ELECTRIC PANEL INSPECTION ELECTRICAL BASICS FEDERAL PACIFIC FPE HAZARDS GROUND SYSTEM INSPECTION KNOB & TUBE WIRING LIGHTNING PROTECTION LOW VOLTAGE BUILDING WIRING MAIN DISCONNECT AMPACITY MULTI-WIRE CIRCUITS PUSHMATIC - BULLDOG PANELS RUST in ELECTRICAL PANELS SAFETY: ELECTRICAL INSPECTION SAFETY Shock Risk Statistics Outside Electrical Inspection Electric Meter & Service Entry Local Electrical Grounding Electrical Panel Interior Inspection Removing Electric Panel Covers Electrical Panel Cover Screws Electrical Panel Interior Hazards Testing Main Breakers or Fuses Inspect Breakers, Fuses, Circuits Testing Receptacles GFCIs AFCIs When to Shut Down Equipment Touching Electrical Equipment Guide to Electrical Test Equipment Using DMMs & VOMs Safely Voltage Measurement & Detection General Electrical Safety Suggestions Electrical Inspection Client Safety SE CABLE SIZES vs AMPS SQUARE-D RECALLS UNDERGROUND SERVICE LATERALS VOLTAGE MEASUREMENT EQUIPMENT ZINSCO / SYLVANIA HAZARDS More Information InspectAPedia Blog - News Updates Air Conditioning & Heat Pumps Bookstore Electrical Environment Exteriors Heating Home Inspection Insulate Ventilate Interiors Mold Inspect/Test Plumbing Water Septic Roofing Structure Accuracy & Privacy Policies Contact Us |
Electrical Safety Hazards and Safe Electrical Inspection Procedures for Electrical Inspectors & Home Inspectors
|
Home Inspection Standards Require Dangerous Activities:
The gruesome death by electrocution shown in the photograph occurred when the man shown tried to steal electrical power from a high voltage cable. - Jim Simmons In a much less serious incident, the author had the personal experience of having a client ask "What's that?" as he reached over our shoulder to stick his finger right into an open fuse socket. Among many reports of fires and accidents whose origin was suspected to be electrical, are reported deaths of a number of electricians and electrical workers - people working in some of the same high-risk areas examined by inspectors. |
Portions of the ASHI Standards of Practice for home inspectors is commented upon below.
ASHI Standards and other building inspection standards are revised from time to time, and the version of Standards discussed here may be obsolete. However the principles discussed and cautions advised will apply to newer versions of building inspection standards as well.
ASHI is the American Society of Home Inspectors - see www.ashi.com. Other home inspection professional associations such as CREIA, NAHI, FABI, TAREI, CAHI, NACHI, and the various U.S. states who license home inspectors have published their own versions of these standards. Home inspection standards are a definition of the scope of practice - what the inspector is obligated to do or not do.
General Electrical Safety Suggestions describes important basic safety procedures, clothing, and equipment for home inspectors and electrical inspectors.
Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.
SAFETY: ELECTRICAL INSPECTION SAFETY
Shock Risk Statistics
Outside Electrical Inspection
Electric Meter & Service Entry
Local Electrical Grounding
Electrical Panel Interior Inspection
Removing Electric Panel Covers
Electrical Panel Cover Screws
Electrical Panel Interior Hazards
Testing Main Breakers or Fuses
Inspect Breakers, Fuses, Circuits
Testing Receptacles GFCIs AFCIs
When to Shut Down Equipment
Touching Electrical Equipment
Guide to Electrical Test Equipment
Using DMMs & VOMs Safely
Voltage Measurement & Detection
General Electrical Safety Suggestions
Electrical Inspection Client Safety
8. System: Electrical Inspection Standards for Home Inspectors (ASHI and other Associations & State Regulations)
8.1.C. [The inspector shall observe] amperage and voltage ratings of the service
|
See Outside Electrical Inspection for details of outside electrical inspection safety procedures. See ELECTRIC METERS & METER BASES for a discussion of examining the electric meter and meter base portion of the service entry. See AMPS & VOLTS DETERMINATION for determining the ampacity of an electrical service: How to determine the electrical Ampacity and Voltage provided to a building discusses in detail how to determine the service amps and voltage by visual inspection. Also see AMPACITY - the LIMITING FACTOR. |
Pay special attention to water entry at the service entry cable, at the top of the electric meter enclosure, and at the wall penetration where the SEC enters the building as these conditions can send water into the electrical panel where corrosion creates unreliable equipment and water is a hazard.
See ELECTRIC PANEL RUST for a study of water entry, rust, and corrosion in electrical panels presented at the 1992 IEEE Holm Conference.
|
Dropped sheet metal screws & loose electric meter boxes: be careful about dropping a metal screw into or onto live electrical parts. If you see that the electrical meter box is loose on the building wall, do not touch it. A loose mounting screw can fall into the meter box, shorting electrical components there and leading to a house fire. -- Arnold Road Poughkeepsie NY house fire - J. Aronstein & D. Friedman. |
See ELECTRIC METERS & METER BASES for procedures used for inspecting these outdoor components.
Details about inspecting electrical grounding and definitions are at GROUND SYSTEM INSPECTION.
8.3.C. [The inspector is NOT required to] dismantle any electrical device or control other than to remove the covers of the main and auxiliary distribution panels.
At least one death, that of an electrician, has been reported to have occurred during the removal of a panel cover
Atlanta GA, a licensed electrician was opening the panel for inspection.] Apparently there was an incipient problem with the spring-loaded bus-bar assembly. When the cover was removed the bus assembly moved, an arc caused an electrical explosion, killing the inspector. -- J. Aronstein to D. Friedman, personal communication, 12/1991.
The following photos and text provide examples of external evidence that may let the inspector avoid trouble or a nasty surprise when inspecting electrical equipment.
The pair of photographs below show two clear warnings that water has been entering an electrical panel - watch out for rust, and for circuit breakers that may not trip in response to an overcurrent, due to internal corrosion.
This defect is not one for which a home inspector (nor most electricians) can reliably test in a home, but the warning remains appropriate. Replace such breakers, and if the electrical panel is badly corroded the entire panel needs replacement.
See RUST in ELECTRICAL PANELS for a detailed account of the sources of water and rust in electrical panels and the frequency of observation of rust and water damage in that equipment.
ASHI Standards 8.1.B [The inspector shall observe] service equipment, grounding equipment, main overcurrent device, main and distribution panels.
|
The pair of photos just below shows at left, electrical arc flashover soot, and at right, the repair - tape on the electrical wire, but the wire is still too close to the screw mounting hole for the panel cover.
Now that we have removed the cover and carefully set the cover and screws aside (don't lose the screws),
8.3.B. [The inspector is NOT required to] test or operate any overcurrent device except Ground Fault Circuit Interrupters
I continued to put my arm behind my back and close the breaker with my left hand with my head turned to the left.
BAM, a light as bright as the sun and an explosion. This knocked us down and blinded us.
We were rushed to the hospital. I spent the night in the ER with an ICU nurse and was off of work for 3 weeks and have had to have a stronger prescription. These FPE panels are all over the building
|
Pulling fuse blocks: At one inspection the author pulled the main fuse block in a 60-Amp panel, only to have the pullout block disintegrate in his hand. The failure left one fuse in place and one half out of the panel. "What did you just do to the panel?" asked the client (from a safe distance). "I destroyed it." was the answer. With permission of the owner, and following accepted home inspection practice of exercising normal user controls intended for use by the homeowner, the home inspector was performing a normal, if uncommon operation which a homeowner would be expected to do, for example, during an emergency or other need to shut off electrical power to the building. At a minimum one would have had to perform this operation during an emergency or if the panel were to be worked on. The client wanted to know if the fuse pullout disintegration was normal. [No.] The inspector wanted to know if he was going to pay for a new panel. [No.] [A new panel was needed as the service and equipment were obsolete, not because the fuse pullout needed replacement.] If you had not pulled the fuse shown at lower right in this photo, something interesting would have been missed. Is that smaller fuse unsafe? What about the other wiring in the panel? Are some of the edison-base fuses oversized? |
More Reading:
Electrical Panels, How to Inspect in Buildings, safety for electrical inspectors, electrical panel, fusing, wiring defects,
8.1.D. [The inspector shall observe] branch circuit conductors, their overcurrent devices, and the compatibility of their ampacities and voltages
In addition to examining the electrical panel before touching it, looking for dangerous conditions like water, rust, sheet metal screws, rats, and blocking client access, the inspector should also recognize that certain brands or models of electrical equipment are known to be unsafe and may be dangerous to inspect or operate.
Federal Pacific Electric Stab-Lok equipment includes breakers which remain internally "on" when switched "off", as well as too often failing to trip off in response to an overcurrent, and which have been reported to result in electrical arc explosions when manually or otherwise exercised.
Zinsco: Similar bus burnups and electrical arc explosions have been reported regarding Sylvania/Zinsco electrical panels.
Contact Us by email to add field reports of problems regarding these or other electrical products.
|
Inspecting overcurrent devices - visual: see ELECTRIC PANEL AMPACITY and ELECTRIC PANEL INSPECTION for detailed procedures. There is a huge amount of information about the electrical system inside of the electrical panels. Reporting unsafe electrical panels: see FEDERAL PACIFIC FPE HAZARDS and see ZINSCO / SYLVANIA HAZARDS The inspector is not required to insert anything, finger, screwdriver, probe, into the electrical panel. The required inspection is visual. Observe. However an inspector is of course permitted to perform other tests or services which s/he chooses to provide (presuming s/he is qualified, trained, and that three are no conflicts of interest). |
|
Reporting aluminum wire: see ALUMINUM WIRING HAZARDS Reporting knob and tube wiring: see KNOB & TUBE WIRING Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website. |
8.1.E. [The inspector shall observe] the operation of a representative number of installed lighting fixtures, switches, and receptacles located inside the house, garage, and on its exterior walls
Also be careful about turning off switches found on. You may damage a computer data base, turn off a heart-lung machine, reset an alarm system, or turn off a marginal switch for the heat that leaves the property with no heat in freezing weather. Be safe and avoid disputes.
An example of accidentally switching off circuits in a building occurs often during removal of an awkward electrical panel cover - it's easy to accidentally push one or more circuit breakers into their off position during cover removal or replacement.
AFCIs: The requirement to inspect and test AFCIs is already in some regulations for home inspectors. It seems likely that remaining home inspection associations and state or provincial inspection standards-writers will soon update their electrical inspection standards section to address the new requirement for AFCI's. See AFCIs ARC FAULT CIRCUIT INTERRUPTERS for details of the electrical code changes regarding the requirement for arc fault interrupters in homes.
AFCIs can be properly tested only by using the test button on the device itself. External tool tests are incomplete and therefore unreliable.
Some inspectors, with adequate training, exceed the requirements of the standards and will actually shut down extremely dangerous equipment themselves.
|
Even the simple task of pulling the cover on a marginal bimetallic stack relay switch on an oil-fired heater can result in failure or inadvertent shutdown of the equipment. Stack relays have a stepping lever which is reset by the service person if the switch, often fragile on old systems, is disturbed. |
Be warned that whether you touch a building component or not there are grave responsibilities.
Touching a building component: if you precipitate a catastrophe, will of course be viewed as a mistake.
Not touching a building component: Failing to act effectively to protect occupants of a building you inspect will, of course, also be viewed as a mistake. If you failed to inspect, detect, report a hazard in a building you may bear liability if later an event occurs.
Disclaimers: A simple disclaimer "not inspected" is in adequate. An adequate disclaimer that meets ASHI standards makes sure that the client understands the significance of an observation [or of steps to omit making an observation].
The last man in rule: Trade and professional education classes concerning mechanical systems, which can involve life-safety concerns, commonly teach the "last man in" rule. Home inspectors know this problem as well. The last "expert" to set foot on the property is vulnerable to blame for any ensuing failures, even if s/he acted entirely correctly and even if s/he never touched the component later in question.
In the final analysis then, the precise safety steps to be taken are up to the judgment of the inspector at the scene. The inspector should also document his or her action. Failing to do anything and failing to even serve notice may be viewed as very dangerous and seriously irresponsible.
With proper training, knowledge, and procedures, electrical inspections can be done safely and accurately. Be careful.
Shocked homeowner: During an inspection an ASHI inspector warned the home owner that there was a short in a florescent ceiling light fixture. The owner, a contractor who had done his own electrical work, irritated and incredulous at this supposed defect, licked his knuckles and bridged a small space between the light body and a nearby gas pipe. He's now a believer. [NOTE: DJF home inspection, Beacon, NY 1990]
Amazing Alk: A very questionable procedure is suggested in The ASHI Training Manual [NOTE: "Electrical Systems," ASHI Training Manual, chapter by Alfred L. Alk, p. 18. ASHI 1987] indicating that the inspector can "test" to see if a panel is dangerously "live" (has an internal short) by tapping the box with the knuckles of his/her right hand to check for current, then laying the right palm on the box to feel for heat before beginning to remove the cover. DO NOT RELY ON THESE UNSAFE METHODS.
From a safety view, this is a bad idea. Never rely on physical touch to judge electrical safety of a component.
Details about the hazards of touching electrical equipment and alternative advice for determining whether or not equipment is safe to inspect are provided at Touching Electrical Equipment.
Also see Guide to Electrical Test Equipment and Using DMMs & VOMs Safely as well as General Electrical Safety Suggestions for electrical inspectors.
Stop, look, listen before touching. More on "just looking" is provided when we discuss opening the electrical panel. Do not rely on touch to determine if electrical equipment is safe. Details about the hazards of touching electrical equipment and alternative advice for determining whether or not equipment is safe to inspect are provided at Touching Electrical Equipment.
|
This is a superb safety tool for testing for the presence of live 120VAC or 240VAC because you do not actually need to touch the tool to anything - just hold the tool near a source of electrical power and the electrical field produced will cause the tool to generate its tone. Faster "ticking" indicates higher voltage; slow ticking can indicate a wire connected to a live circuit even if the wire is not presently conducting current. With practice the inspector can guess the voltage level from the tone quality. We use this tool to check light sockets for power when there is no bulb or the bulb is dark. We also use this tool to look for lost or hidden wiring in walls and ceilings. Its sensitivity falls off with the square of the distance from the source of electrical power. Weird and interesting behavior of the TIF Tic Tracer: Some ASHI NE chapter inspectors pointed out that this device can be "fooled" into thinking that a wire scrap is "live" or that even a pipe is electrically "live" when it is not. If a live electrical wire passes close enough to another metal device such as a pipe, electrical conduit, or armored cable, the metal device, conduit, or cable may pick up the electrical field generated by the "live wire" and appear "live" itself when it is not. (This is a "safe" error in that it errs in the direction of warning that something is live when it is not.) This tool will also respond to momentary static electricity. In winter, simply rubbing its tip quickly across a wall can produce a momentary sound response. (Which can be fun in certain circumstances.) The Tic Tracer™ is discussed further at TOUCHING EQUIPMENT. Inspectors who object to the "false positive" possibility make use of a light-pen or similar tool which performs similar functions with less sensitivity to false positives. |
|
Just touch one leg of the tester to the surface to be checked (a wire terminal or an electrical panel enclosure). Touch the second leg of the neon tester to a sure-ground such as a water pipe that you see continues into soil. If voltage is present within the range of sensitivity of the neon tester's bulb, the bulb will light. We discuss neon testers for voltage at Electrical Tools Every Homeowner Should Have |
|
Receptacle testers are used by most home inspectors to check for proper wiring at electrical receptacles as well as to check the function of GFCI's. For testing AFCI's the only reliable test currently available is the device's own test button. We provide details about using receptacle testers at Electrical Tools Every Homeowner Should Have |
Neither of these neat little electrical test tools can be relied on to report low levels of current leakage.
At an investigation of a garage roof that shocked a crew of builders during reconstruction after a lightning strike, we measured voltage varying between about 38 volts AC and 68 volts AC between some framing components and the earth. We could not detect these conditions with a neon tester. A VOM or DMM was needed.
|
NOTE: Once having tested at the highest voltage range, greater accuracy may be obtained by choosing more sensitive ranges which permit readings to be taken in the upper portion of the scale. Disconnect the test probes (or shut off the voltage source) before changing the voltage range setting on the VOM. Details on safe use of DMM's and VOMs are at Using DMMs & VOMs Safely. |
For example, if the meter indicates more than 1or 2 volts between a service panel cover and ground, there's a safety problem. Most low-cost analog-type meters such as the one described provide additional ranges used to read lower voltages with more sensitivity.
Some VOM models provide alligator clips for the ends of the test probes. These clips permit measuring high voltage without handling the probes. Always shut off the power before connecting the alligator clips.
8.3 During an electrical system inspection the inspector is NOT required to
8.3.A. insert any tool, probe, or testing device inside the panels
|
Use only DMM's (digital multi meters) or VOMs (volt-ohm meters, the analog predecessors to DMMs) designed for high energy measurements. Details about safe use of VOMs and DMMs are provided at Using DMMs & VOMs Safely. |
These electrical inspection suggestions are not a complete inventory of all electrical components that should be inspected; these notes focus on identification of conditions that may present special electrical hazards for the electrical inspector. Contact Us by email to suggest changes, corrections, and additions to this material.
Pay attention, look carefully, move slowly before opening or exploring electrical equipment. Learn to recognize indications of a problem, such as but not limited to the examples in this article.
Do not assume anything when performing dangerous tasks such as inspecting electrical equipment.
Do not touch live wires or connections. Watch your hands and other body parts. Handling live electrical wires without special training and equipment is highly questionable and often fatal.
December 12, 1988 - Madison, WI - Michael E. Hammes, 26, died in an apparent electrocution while working in Madison. Hammes had been hired by CUNA Mutual Insurance Society to change ballasts on fluorescent lights. Authorities said he was replacing a fixture in a fourth floor bathroom while standing on a stepladder when he slumped to the floor.
Hammes apparently was electrocuted when he touched live wire with one hand and a metal partition with his body or other hand, according to Dana County Coroner Ray Wosepka.
Hammes was a first-year electronics student. Wosepka said his investigation showed the light fixture had been properly wired. Hammes apparently replaced a ballast, a [transformer] that controls the electrical flow to the light bulbs, and was attaching the live wire when it electrocuted him, Wosepka said. -- Ibid.
If in your opinion unsafe conditions exist at a property you are inspecting you should notify all parties concerned, including building occupants/management/owners, realtors involved, and other appropriate authorities.
December 18, 1988 - Smyrna, GA - A Smyrna family's troubles with a faulty circuit breaker in their mobile home ended in tragedy when a fire broke out and killed 18-year-old Jeffrey Scott Auton. Auton's family, experiencing problems with the main circuit breaker, went to a home products store to buy a new one for their trailer, said Fire Investigator David Herndon.
The store did not have a circuit breaker to fit the family's needs and a new one had to be ordered. .... Herndon said the fire was started when the circuit breaker shut down completely as three space heaters were running. The family had a history of problems with the breaker, particularly from a load put on it by a large heating unit. Herndon stated that after the fire there was not a trace left of the circuit breaker; it was completely gone from
the panel. -- Ibid.
For example, what if the case above had happened the day after the property described had been examined by an ASHI inspector? Were there perhaps clues which telegraph a developing problem? What about anecdotal reports from the occupants of recurrent breaker tripping, visible signs of overheating in the panel, widespread and unusual use of electric heaters, or evidence of work in the panel by untrained people? These risks to occupants are also a hazard to the inspector on several bases.
Protect yourself and your client from injury using but not limited to the suggestions we provide here and just below.
OPINION-RC: "As a master electrician, here is how I teach opening a service panel in my seminars: "The lucky 7""
Further Safety Warning--DF: these are helpful electrical safety suggestions from an experienced electrician. No list of suggestions is incomplete and these presume that they are being followed by an experienced, licensed electrician.
For example, there are almost certainly gloves and/or boots specifically recommended for this application; there are specific safety details to look at and for before touching an electrical panel, and procedures for using electrical test equipment to test or examine a suspect electrical panel.
Rex Cauldwell's Wiring A House - available online.
Rex Cauldwell's Safe Home Wiring Projects - available online
Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.
A home inspector or electrical inspector who has reported a very unsafe condition, recommended immediate action, and yet may later learn that occupants of the building were nearly killed by work by an incompetent repairman. [NOTE: Port Jervis, NY, AHS Ctl#4658911, 7/10/90.] What can be done to reduce the chance of this terrible consequence?
Recommending action on an unsafe condition can convert a pre-existing problem into an immediate catastrophe if the client or owner calls an untrained person to the property or if he attempts a do-it-yourself repair.
Often a referral to local fire inspector, electrical inspector, or utility company can help assure that repairs are prompt, proper, and safe. If you recommend immediate action for an unsafe condition, where possible you should provide some means for the client or building owner to assure that the action which is taken is proper and safe.
Inspectors are properly nervous and reluctant to prescribe the actual repair that is needed at a property - they may not know the detailed repair procedure, or there may be alternative repairs, or their description may prompt an un-trained person to try to do the work.
The inspector should inform the appropriate parties both orally and in writing any suspected unsafe conditions.
If an area or component could not be fully inspected, the inspector should explain in writing why she or he did not enter or examine an area or component, and what additional inspections or steps should be taken, as well as the general risks that may be present.
If in the inspector's judgment equipment is an immediate threat to life and property, such as a boiler whose flue connection has fallen off, we recommend that dangerous equipment be shut down and the appropriate people notified. See Shutting Down Unsafe Equipment. In some cases "appropriate people" includes not only the client and building owner, but also building occupants.
In some instances such as sparking electrical panels, gas leaks, or evidence of a fire, the inspector and everyone else should leave the building immediately and from outside, call the fire department and as appropriate, the gas company, police, or rescue personnel.
...
Search InspectAPedia |
High-tension current generally causes the most serious injuries, although fatal electrocutions may occur with household current (eg, 110 V in the United States and Canada and 220 V in Europe, Australia, and Asia). Contact with alternating current at 60 cycles per second (the frequency used in most US household and commercial sources of electricity) may cause tetanic skeletal muscle contractions, preventing self-release from the source of the electricity and thereby leading to prolonged exposure. The repetitive frequency of alternating current also increases the likelihood of current flow through the heart during the relative refractory period (the "vulnerable period") of the cardiac cycle. This exposure can precipitate ventricular fibrillation (VF), which is analogous to the R-on-T phenomenon.-- circ.ahajournals.org - September 2008
|
|
![]() The Mold Information Center: What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems |
![]() Use this simple, economical mold test kit by following our instructions on how to collect and mail mold samples to our lab |
Environmental Inspection, Testing, & Diagnosis On-Site IAQ, Gas, Air Testing, Mold Investigation, Sick Building Diagnosis, Lab Services, & Remediation Plan Preparation - indoor air quality testing, problem source determination, supporting lab work, written remediation plan addressing removal of environmental and other hazards and prevention of their recurrence.
|
![]() Building Inspection, Problem Diagnosis, Forensic Investigation & Testing, Repair Consulting |
|
|
11/20/2008 - 03/28/1992 - InspectApedia.com/electric/ElecSafety.htm - © 2009 - 1988 Copyright Daniel Friedman All Rights Reserved - InspectAPedia® is a Registered U.S. Trademark