FPE Stab-Lok CPSC Calibration Tests FPE Stab-Lok HAZARDS & REPAIRS WEBSITE SUMMARY OF the FPE Stab-Lok PROBLEM FPE HAZARD ARTICLES, STUDIES FPE Stab-Lok TECHNICAL REPORT HOW TO IDENTIFY FPE & FP REPORTS OF FPE FAILURES HOW TO REPORT FPE INCIDENTS FPE REPAIR ELECTRICIANS FPE REPLACEMENT BREAKERS FPE REPLACEMENT PANELS FPE REPLACEMENT PANEL COSTS CAN'T AFFORD A NEW ELECTRIC PANEL? FEDERAL PIONEER in CANADA FPE Stab-lok: FIRES WAITING TO HAPPEN ADVICE TO HOME BUYERS w/ FPE PANELS HOME INSPECTION LANGUAGE for FPE Stab-Lok IAEI LETTER More Information Mobile View InspectAPedia Blog - News Updates Air Conditioning & Heat Pumps Bookstore Electrical Environment Exteriors Heating Home Inspection Insulate Ventilate Interiors Mold Inspect/Test Plumbing Water Septic Roofing Structure Accuracy & Privacy Policies Contact Us |
CALIBRATION AND CONDITION TESTS OF MOLDED CASE CIRCUIT BREAKERS - Federal Pacific Stab Lok Breakers - CPSC Data
| ||||||||||||||||||||||||||||||
|
FAILURE CONDITION |
FAILURES |
|
|
% (#failed/#tested) |
||
|
Before Mechanical Operations |
After Mechanical Operations |
|
|
No-trip: 200% of rating, both poles |
0% (0/122) |
1% (1/107) |
|
No-trip: 200% of rating, individual poles |
1% (3/244) |
10% (21/214) |
|
No-trip: 135% of rating, both poles* |
25% (31/122) |
36% (39/107) |
|
No-trip: 135% of rating, individual poles |
51% (125/244) |
65% (144/220) |
|
Trip: 100% of rating, both poles* |
3% (4/122) |
6% (7/111) |
|
Dielectric Breakdown (short)* |
0 |
1% (1/111) |
|
TABLE 1 - SUMMARY OF FAILURES *UL 489 Test Conditions | ||
The failures appeared. among breakers of all ratings, none were failure-free. Most of the "no-trip' conditions were sustained for four hours well beyond the UL specification. These were not marginal failures with respect to the failure criteria. The data suggests that, on the average, the mechanical operations result in increased failures. This was .'not strictly the case on a sample-to-sample basis.
The failures relate to hazardous conditions in at least two ways. First, a fault in the wiring or utilization equipment which causes excessive- current-can result in fire if the circuit is not opened by the breaker -- this is its principal functional requirement.
Secondly, it was determined in these tests that some of the breakers overheat to hazardous levels when subjected to overcurrent conditions (due to their own failure to trip) for sustained periods of time.
The overheating can result in incapacitation of the breaker (i.e.: it will no longer open under any condition), and the temperature can be high enough to ignite fire in the vicinity of the breaker, as evidenced by charring of the case on some samples.
NOTE: this text is quoted verbatim from pages 3-5 of "Calibration and Condition Tests of Molded Case Circuit Breakers, Final Report: Contract CPSC-C-81-1429 December 30, 1982," obtained from the US Consumer Product Safety Commission as a FOIA request.
...
Search InspectAPedia |
Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.
|
|
![]() The Mold Information Center: What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems |
![]() Use this simple, economical mold test kit by following our instructions on how to collect and mail mold samples to our lab |
Environmental Inspection, Testing, & Diagnosis On-Site IAQ, Gas, Air Testing, Mold Investigation, Sick Building Diagnosis, Lab Services, & Remediation Plan Preparation - indoor air quality testing, problem source determination, supporting lab work, written remediation plan addressing removal of environmental and other hazards and prevention of their recurrence.
|
![]() Building Inspection, Problem Diagnosis, Forensic Investigation & Testing, Repair Consulting |
|
|
04/15/2009 - 08/11/99 inspect-ny.com/fpe/CPSCsummary.htm -- Web Page Design © 2009 - 1999 Dan Friedman All Rights Reserved