FPE Stab-Lok HAZARDS & REPAIRS WEBSITE SUMMARY OF the FPE Stab-Lok PROBLEM FPE HAZARD ARTICLES, STUDIES FPE Stab-Lok TECHNICAL REPORT HOW TO IDENTIFY FPE & FP REPORTS OF FPE FAILURES HOW TO REPORT FPE INCIDENTS FPE REPAIR ELECTRICIANS FPE REPLACEMENT BREAKERS FPE REPLACEMENT PANELS FPE REPLACEMENT PANEL COSTS CANADIAN VERSIONS FPE Stab-lok: FIRES WAITING TO HAPPEN ADVICE TO HOME BUYERS w/ FPE PANELS HOME INSPECTION LANGUAGE for FPE Stab-Lok IAEI LETTER More Information InspectAPedia TM Home & Site Map Air Conditioning InspectAPedia Bookstore Electrical Environment Exteriors Heating Home Inspection Insulate Ventilate Interiors Mold Inspect/Test Plumbing Water Septic Roofing Structure Accuracy & Bias Pledge Contact Us |
Consumer Note: replacement FPE Stab-Lok circuit breakers are unlikely to reduce the failure risk of this equipment. We recommend replacing the Federal Pacific Electric Stab-Lok panel entirely. Our site offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at inspect-ny.com/appointment.htm.This website explains the fire and shock hazards associated with Federal Pacific Electric Stab-lok circuit breakers and service panels, provides a history of the issue, recounts research on FPE failures, and recommends replacement of the panels. panel replacement or repair. The web author has no business, financial, or other connection with FPE products nor with their replacement. Electronic copies and reproduction of this information at other websites are prohibited. Readers are welcome to make and distribute printed copies of our articles about FPE Stab-Lok equipment provided this web page is cited and provided that the content is not edited or changed. (Contact us to suggest edits, changes, corrections, updates). © Copyright 2008 Daniel Friedman, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use the links at page left to navigate this document or to go to Other Website Topics. Green links at left show where you are in our document & website. Letter to IAEI International Association of Electrical Inspectors News Magazine re: FPE Public Relations Article asserts Federal Pacific Electric Stab-Lok panels are OK.8/11/99
International Association of Electrical Inspectors Dear Mr. Cox: The May/June '99 IAEI News article by an unidentified FPE consultant asserts that Federal Pacific Electric Stab-Loks are UL-Listed and thus without any concern. The article fails to address a record of failures to trip, actual test results, field reports of failures, and improper UL listing practices. The FPE author and IAEI News failed to report on the actual website content, failed to contact the author, and failed to give the correct website address so that readers could judge for themselves. I am an IAEI member and the author of the informational website for home inspectors which was referred-to in the FPE article. The correct Internet website address is http://www.inspect-ny.com/fpe/fpepanel.htm Publicly available information is compelling and sufficient to warrant warning contractors, inspectors, and consumers. The best data available substantiates that the 2-pole breakers cannot be relied upon to trip. CPSC found that was the case. FPE agreed that was the case. Field reports confirm that is still the case. Inspectors should work towards replacing breakers that won't trip, not towards whitewashing the problem. The problem with FPE breakers is that a significant portion of them will not trip on overload or short circuit conditions in order to protect a building from fire ignition. Testing done by the CPSC showed that at a modest overload on both poles these failed 25% of the time, followed by a lockup. The breaker would never trip in the future at any overload. (See Table 1, Summary of Failures, CPSC-C-81-1429 December 30, 1982, attached.) There are other types of failures known to occur in FPE panels at lower probability and not as well documented as the 2-pole no-trip problem. FPE did not refute the CPSC's test data. The no-trip problems with 2-pole Stab-Lok breakers were acknowledged by FPE. FPE claims that when their circuit breakers do not trip it does not constitute a hazard. The article in IAEI News by FPE is asking us to agree with FPE's position that breakers that won't trip are OK because they are "listed and labeled." Let's keep in mind that a breaker that will not trip on certain overcurrent conditions is electrically the same as an Edison-base fuse with a penny behind it. No inspector should be encouraged to condone or whitewash the continued use of breakers that cannot be depended on to trip properly. These problems were known. Reliance Electric Co. had bought FPE in 1979 when they discovered problems with FPE breakers. They sued the company they had bought FPE from, claiming undisclosed potential liability made FPE not what they had bargained for and citing evidence that "improper and deceptive practices were employed for many years to secure UL listings for Federal Pacific's circuit protective products? They wanted their money back. Reliance eventually settled the suit, kept FPE, and got back $41.85 million in return for which they agreed to indemnify the company they'd bought FPE from for product liability claims arising from products made by FPE before the purchase. Continuing problems can't be ruled out. For example, see the Federal Pacific/Federal Pioneer circuit breaker warranty alert issued by the Ontario New Home Warranty Program in 1997 (copy attached). These products are still present in the field! Reports from consumers and electricians indicate failures to trip, overheating, and fires. Note also that the author of the FPE article did not want to have his or her name associated with it and that the FPE contact listed is an attorney retained (presumably) by FPE. The information address given in the article would have been more accurate if given as: Howard B. Abramoff Law Offices, 25700 Science Park Dr. Suite 260, Cleveland OH 44122. This is a law firm, not a circuit-breaker manufacturer. This confirms that the article is biased towards the defense of FPE rather than providing information on "?the safe installation and use of electricity" (IAEI's mission statement in the magazine's masthead). As a neutral professional, I'd be pleased to receive reliable information shedding new light on the situation. But a public relations article written by someone whose aim is to protect FPE's interests and which fails to address legitimate concerns and the known failures and problems occurring around the country is not something I'd rely upon. Based on my experience and numerous reports from people with no axes to grind, it appears that FPE circuit breakers frequently fail to perform their function. A circuit breaker may sit in a building for twenty years, and as long as it never sees an overload or short circuit it may seem to work fine. But if it cannot perform its function to interrupt current when overloaded or short circuited, that circuit breaker is a latent fire hazard. Such equipment should be replaced. Respectfully, Dan Friedman, IAEI #195930 Attachments: 1. "Calibration and Condition Tests of Molded Case Circuit Breakers, Final Report: Contract CPSC-C-81-1429," December 30, 1982, Wright Malta Corporation, Summary Pages 1-3. 2. Reliance Electric Co. Press Release, July 7, 1980, stating that "Underwriters Laboratories labels for most of FPE's circuit breakers were obtained through improper practices,? 3. Schneider Electric Canada Warranty Alert, recalling Federal Pioneer (Federal Pacific Canadian) circuit breakers NC015/NC015P, October 14, 1997 4. My resume/background (Since the article indicates the author did not know who I am) 5. WEB FaqS: Website author, credibility 6. "Federal Pacific Electric (FPE) Panels, a Summary," website page from http://www.inspect-ny.com/fpe/fpepanel.htm (This is the root page of a collection of public documents and articles regarding this topic.) 06/01/07 follow up note: IAEI and Mr. Cox have not replied to this correspondence.
Technical ReviewersParticular thanks are due to experts and also consumers who read these articles and suggest corrections, changes, and additions to the material. Content suggestions, technical corrections and content critique are invited for any of the content at our website.
| |
|
FPE Stab-Lok HAZARDS & REPAIRS WEBSITE SUMMARY OF the FPE Stab-Lok PROBLEM FPE HAZARD ARTICLES, STUDIES FPE Stab-Lok TECHNICAL REPORT HOW TO IDENTIFY FPE & FP REPORTS OF FPE FAILURES HOW TO REPORT FPE INCIDENTS FPE REPAIR ELECTRICIANS FPE REPLACEMENT BREAKERS FPE REPLACEMENT PANELS FPE REPLACEMENT PANEL COSTS CANADIAN VERSIONS FPE Stab-lok: FIRES WAITING TO HAPPEN ADVICE TO HOME BUYERS w/ FPE PANELS HOME INSPECTION LANGUAGE for FPE Stab-Lok IAEI LETTER More Information InspectAPedia TM Home & Site Map Air Conditioning InspectAPedia Bookstore Electrical Environment Exteriors Heating Home Inspection Insulate Ventilate Interiors Mold Inspect/Test Plumbing Water Septic Roofing Structure Accuracy & Bias Pledge Contact Us |
More Information on Federal Pacific Electric Stab-Lok Panel Electrical Hazards & on Building Diagnostic Inspections and Repairs
06/01/07 -- © 2007 - 1999 Copyright Daniel Friedman All Rights Reserved. Citation by brief quote or links-to this website are invited, provided you credit this source website www.inspect-ny.com/fpe/FPE_IAEI.htm Please do NOT copy and reproduce our full articles without calling first to obtain express permission. |