THE FPE Stab-Lok WEBSITE
SUMMARY OF the FPE Stab-Lok PROBLEM
FPE HAZARD ARTICLES, STUDIES
FPE Stab-Lok TECHNICAL REPORT
HOW TO IDENTIFY FPE & FP
REPORTS OF FPE FAILURES
HOW TO REPORT FPE INCIDENTS
FPE REPAIR ELECTRICIANS
FPE REPLACEMENT BREAKERS
REPLACEMENT PANELS
  OPTION #1 RETROFIT KIT
  OPTION #2 REPLACEMENT
  OPTION #1 vs OPTION #2
FPE REPLACEMENT PANEL COSTS
CANADIAN VERSIONS
FPE Stab-lok: FIRES WAITING TO HAPPEN
ADVICE TO HOME BUYERS w/ FPE PANELS
HOME INSPECTION LANGUAGE for FPE Stab-Lok
More Information

InspectAPedia TM Home & Site Map
Electrical
Accuracy & Bias Pledge
Contact Us


Photograph of  Eaton Cutler Hammer Electric Retrofit Kit for Electrical Panel Replacement REPLACEMENT PANELS - Cutler Hammer's Options Replace Federal Pacific Electric FPE Stab-Lok Electric Panels
FPEaPedia ©

Google
 
  • Eaton Cutler Hammer replacement panel choices for Federal Pacific Electric Stab-Lok equipment
  • Replacement FPE Stab-Lok electrical panels
  • Replacement FPE Stab- Lok circuit breakers?
We recommend against replacing individual FPE Stab-lok circuit breakers - there is no evidence that doing so will improve the safety of the electrical system. We recommend that the panel be replaced entirely. Our site offers impartial, unbiased advice without conflicts of interest. Our site offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at inspect-ny.com/appointment.htm.

This document describes how to replace Federal Pacific Stab-Lok Electric Panels in buildings. We describe two methods for correcting this safety hazard in buildings. Option 1 - replacement of the panel bus assembly or "load center" while leaving the original electrical panel enclosure or "box" and its attached wires intact, by using the Eaton Corp., Cutler Hammer Products "Adjustable Retrofit Kit" and Option 2 - conventional removal and replacement of the entire electrical panel.

Where the original panel enclosure is in good condition, Option 1 should cost less and be a faster job than Option 2 because less labor and less disruption is involved. We do not recommend mere replacement of FPE Stab-Lok circuit breakers themselves, as discussed at the REPLACEMENT BREAKERS link at below-left. This is information for building inspectors, home buyers, home owners, and electricians regarding steps to reduce the hazards associated with Federal Pacific Electric Stab-lok circuit breakers and service panels. Safety warning: as with any electrical installation or repair, these steps must be performed by a licensed and qualified electrician and must comply with appropriate building codes and regulations. Good workmanship and an accurate assessment of the condition of the electrical panel enclosure which is to be re-used are important for FPE Electric Panel . Also see THE FPE Stab-Lok WEBSITE - the main FPE Hazard Website. © Copyright 2008 Daniel Friedman, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use the links at page left to navigate this document or to go to Other Website Topics. Green links at left show where you are in our document & website.

REPLACEMENT PANELS - Alternative Methods for Replacement of Federal Pacific Stab-Lok (FPE) Electric Panels

Safety Notice:: working with electrical equipment can involve fire, and fatal shock hazards. Electrical repairs must be performed by a qualified, licensed professional electrician. Good workmanship, following manufacturer's instructions, and local and other appropriate code compliance are also essential for a safe and successful outcome.

The first section of this document OPTION #1 RETROFIT KIT describes how to replace Federal Pacific Stab-Lok Electric Panels in buildings using a retrofit kit provided by Eaton Corp., Cutler Hammer Products (E-CH): Option 1 - replacement of the panel bus assembly or "load center" while leaving the original electrical panel enclosure or "box" and its attached wires intact, by using the Eaton Corp., Cutler Hammer Products "Adjustable Retrofit Kit" and

In a second document section OPTION #2 REPLACEMENT we discuss Option 2 - conventional removal and replacement of the entire electrical panel.

In a third document section OPTION #1 vs OPTION #2 we express an opinion which compares these two methods.

Where the original panel enclosure is in good condition, Option 1 should cost less and be a faster job than Option 2 because less labor and less disruption is involved. We do not recommend mere replacement of FPE Stab-Lok circuit breakers themselves, as discussed at the REPLACEMENT BREAKERS link at below-left.This is information for building inspectors, home buyers, home owners, and electricians regarding steps to reduce the hazards associated with Federal Pacific Electric Stab-lok circuit breakers and service panels. Safety warning: as with any electrical installation or repair, these steps must be performed by a licensed and qualified electrician and must comply with appropriate building codes and regulations. Good workmanship and an accurate assessment of the condition of the electrical panel enclosure which is to be re-used are important for FPE Electric Panel


THE FPE Stab-Lok WEBSITE
SUMMARY OF the FPE Stab-Lok PROBLEM
FPE HAZARD ARTICLES, STUDIES
FPE Stab-Lok TECHNICAL REPORT
HOW TO IDENTIFY FPE & FP
REPORTS OF FPE FAILURES
HOW TO REPORT FPE INCIDENTS
FPE REPAIR ELECTRICIANS
FPE REPLACEMENT BREAKERS
REPLACEMENT PANELS
  OPTION #1 RETROFIT KIT
    WHY IT WORKS
    RETROFIT COST
    RETROFIT INSTALLATION
    COMPONENT SELECTION
    PRODUCT SOURCES
    CODE COMPLIANCE
    BACKGROUND
  OPTION #2 REPLACEMENT
  OPTION #1 vs OPTION #2
FPE REPLACEMENT PANEL COSTS
CANADIAN VERSIONS
FPE Stab-lok: FIRES WAITING TO HAPPEN
ADVICE TO HOME BUYERS w/ FPE PANELS
HOME INSPECTION LANGUAGE for FPE Stab-Lok
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

OPTION #1 RETROFIT KIT - Federal Pacific Electric Panel Replacement - Option #1 Using the Eaton Corp., Cutler Hammer Products Adjustable Retrofit Kit

Adjustable Retrofit Kits produced by Eaton Corp., Cutler Hammer Products (E-CH) are a patented design new electric panel interior designed to replace aging electrical panels in residential and light commercial applications. The unique features are that the existing box and wiring can be re-used for convenience, if still in good working condition. Also, a custom trim to fit the existing box is available.

Using the retrofit kit involves disconnecting the electrical circuits from the existing load center "bus assembly"circuit breakers. The old bus assembly and other internal parts (neutral bus, ground bus, etc) in the existing panel are removed. The panel box or "enclosure" itself is left in place, and the electric circuit wires which entered that box are left undisturbed.

After inspection by the installer to confirm the soundness of the panel box, any openings in the box body are closed, a new load center (panel bus and circuit breaker set, ground and neutral bus bars) is mounted in the existing electric panel box, and the existing circuits are connected to the new circuit breakers.

The "field adjustable electric panel interior assembly" consists of an adjustable riser, the required interior bus assembly, and the appropriate neutral assembly and ground bar assembly. Additional kit components permit a new panel face to correctly fit the new bus assembly which has now been mounted in the old panel box.

On completion, all of the electrical parts inside the original electric panel have been replaced. Only the steel panel enclosure or "box" has been retained. The new parts and installation are made using UR and UL approved components. Wiring to comply with the electrical code, workmanship, and final code approval are the responsibility of the installing electrician, assured by an inspection by the local electrical inspector.

Not all Electrical Panels can be Upgraded using the Retrofit Kit

Field reports and comments from the manufacturer have pointed out that not every elecrical panel is a candidate for upgrading using the retrofit kit discussed here. If the original electrical panel enclosure is itself too small to meet the size and space requirements of current electrical codes the entire panel will need to be replaced.

The following text provides an example of a case where, unfortunately, the old electrical panel was just too small to upgrade:

From email between a reader and the product manufacturer
While researching the service panel in a home I purchased this summer, I came across your retrofit kit for FPE service panels at http://www.inspect-ny.com/fpe/fpereplace.htm
I have a Stab-Lock C1410-14-125NI panel, 125amp, 120/240, 1 phase 3 wire. It currently has one 30a (dryer), one 40a (range) and one 50a (all other circuits) controlling 6 15a and 4 20a. I would like to upgrade to 150amp with a few more breaker spaces, if possible.
The box measures 4 inches deep, 10 inches wide, 22-3/4 inches high inside measurements. The load center w/breakeres is approximately 6-1/2inches wide by 15 inches high.
The range wire is aluminum. I'm not sure if the incoming service wires are aluminum as well. The home was built in 1960. The existing panel is in excellent condition, no rust, all holes intact or in use. The existing wiring is in excellent shape.
One local electrician told me that your product violates code.

Here is a clear and concise reply from the manufacturer:

Our retrofit kits are designed to be installed into enclosures where there is sufficient space to wire according to the National Electric Code. As the local electrician pointed out, the enclosure that you have is not large enough to allow for our kits to work. Being from 1960, the existing electrical panel was constructed prior to two NEC revisions that expanded the necessary wire bending space requirements. In addition, to increase the ampacity of the panel would require slightly more space. Unfortunately, for the application described, a new service will need to be installed.


THE FPE Stab-Lok WEBSITE
SUMMARY OF the FPE Stab-Lok PROBLEM
FPE HAZARD ARTICLES, STUDIES
FPE Stab-Lok TECHNICAL REPORT
HOW TO IDENTIFY FPE & FP
REPORTS OF FPE FAILURES
HOW TO REPORT FPE INCIDENTS
FPE REPAIR ELECTRICIANS
FPE REPLACEMENT BREAKERS
REPLACEMENT PANELS
  OPTION #1 RETROFIT KIT
    WHY IT WORKS
    RETROFIT COST
    RETROFIT INSTALLATION
    COMPONENT SELECTION
    PRODUCT SOURCES
    CODE COMPLIANCE
    BACKGROUND
  OPTION #2 REPLACEMENT
  OPTION #1 vs OPTION #2
FPE REPLACEMENT PANEL COSTS
CANADIAN VERSIONS
FPE Stab-lok: FIRES WAITING TO HAPPEN
ADVICE TO HOME BUYERS w/ FPE PANELS
HOME INSPECTION LANGUAGE for FPE Stab-Lok
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

WHY IT WORKS - Key Features of the E-CH Adjustable Retrofit Kit

Key in making this retrofit approach possible in the replacement of FPE or other problematic electrical panels is E-CH's development of:

  1. Load Centers: a series of replacement load centers of varying capacity in amperage and number of circuit breakers, and varying also in overall dimensions
  2. The Adjustable Retrofit Kit: which offers a set of parts which permit the new load center, mounted in the old electric panel enclosure, to be framed-in or enclosed properly regardless of the dimensions of the enclosure itself. The electrician simply measures the existing enclosure and orders the appropriate load center and adapter kit parts. The Adjustable Retrofit Kit parts may include:
    • A "picture frame" which adapts the existing enclosure to allow a new "trim/cover" assembly to be mounted as seen in the figure on page 2 of the E-CH product PDF file available here (450KB to download). The "picture frame" is .073 powder coat painted galvanized steel which not only adapts the trim to the existing enclosure, it extends past the enclosure edge several inches to provide a professional looking finish when the old plaster or drywall is damaged.
    • An adjustable "riser" combined with the adjustment feature in the deadfront solves the depth issues and helps greatly when the old enclosure was not installed plumb/square.
    • The "trim/cover assembly" is the standard replacement loadcenter/panelboard trims that offered by CH as replacement items and as such carry the standard UL cabinet front label.

One of the biggest hurdles the manufacturer faced was the panel enclosure depth issue. To solve this, CH offers the adjustable depth feature. This allows the "riser" to be adjusted to accommodate enclosures from 4" to 6" in depth. When this is combined with the "picture frame" and "trim" the final product is a very safe, solid, and professional looking final assembly. To date (June 2006) CH engineers have not had any reports of any brand or model specific enclosure that these have not worked in. Due to the adjustability of the CH kit, it is unlikely there would be an electric panel model that these kits wouldn't fit.

Very shallow panel enclosures:

Eaton Corp., Cutler Hammer Products have just finished the design & patent work on phase 2 of this program. This will consist of an adjustable "extension collar" which will attach to the enclosure and extend it out from the wall for those installations that are very shallow. This will extend them out and then the standard "Retrofit Kit" can be used. This will accommodate enclosures clear down to 3" or less in depth.

More Reading:
Eaton Corp., Cutler Hammer Products Adjustable Retrofit Kit Ordering Instructions PDF file 450KB to download.


THE FPE Stab-Lok WEBSITE
SUMMARY OF the FPE Stab-Lok PROBLEM
FPE HAZARD ARTICLES, STUDIES
FPE Stab-Lok TECHNICAL REPORT
HOW TO IDENTIFY FPE & FP
REPORTS OF FPE FAILURES
HOW TO REPORT FPE INCIDENTS
FPE REPAIR ELECTRICIANS
FPE REPLACEMENT BREAKERS
REPLACEMENT PANELS
  OPTION #1 RETROFIT KIT
    WHY IT WORKS
    RETROFIT COST
    RETROFIT INSTALLATION
    COMPONENT SELECTION
    PRODUCT SOURCES
    CODE COMPLIANCE
    BACKGROUND
  OPTION #2 REPLACEMENT
  OPTION #1 vs OPTION #2
FPE REPLACEMENT PANEL COSTS
CANADIAN VERSIONS
FPE Stab-lok: FIRES WAITING TO HAPPEN
ADVICE TO HOME BUYERS w/ FPE PANELS
HOME INSPECTION LANGUAGE for FPE Stab-Lok
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

RETROFIT COST - Cost of Replacing an FPE Panel using the E-CH Adjustable Retrofit Kit

Cutler Hammer was unable to inform me of "typical" retrofit installation costs using their product. Electrical panel replacement costs are hard to cite as there really isn't a typical application for this product - it is used in a wider variety of circumstances than just replacement of FPE Stab-Lok electrical panels. These vary from the smallest single phase, main lug, 125amp units to the largest three phase, main breaker, 42-circuit. 225-AMP kits. (Probably the manufacturer did not want to appear to set the retail prices charged by the electricians who buy their product.)

In addition, custom size adapter collars can add to the costs as well. Materials costs typically run from $225 to $500 per kit plus installation cost. From the feedback CH has received from the field, when you figure in labor, the installed kit is less than half the cost of Option #2 - complete removal and replacement of the electrical panel. That is exactly in line with my own (DJF's) guess based on the labor and building disruption savings. If there is much cosmetic work with the Remove-and-Replace process, the savings are even greater.

Quotes from electrical contractors on FPE electrical panel replacement using the retrofit kit or using a complete new replacement electrical panel can be expected to vary by area of the country, hardware needed, replacement panel size in ampacity and number of circuits, accessibility to perform the work, and other factors that affect labor or materials.

That said, we've heard FPE panel replacement costs using the Cutler Hammer retrofit panel ranging from about $900. all the way up to $4000. If you are surprised by the quotation you receive from your electrician, ask for a bid from a competitor and compare labor, materials, and other costs.

"REPLACEMENT COST Typical cost of the traditional FPE Electrical Panel Replacement" discusses the costs of FPE panel replacement using a completely new electrical panel assembly.


THE FPE Stab-Lok WEBSITE
SUMMARY OF the FPE Stab-Lok PROBLEM
FPE HAZARD ARTICLES, STUDIES
FPE Stab-Lok TECHNICAL REPORT
HOW TO IDENTIFY FPE & FP
REPORTS OF FPE FAILURES
HOW TO REPORT FPE INCIDENTS
FPE REPAIR ELECTRICIANS
FPE REPLACEMENT BREAKERS
REPLACEMENT PANELS
  OPTION #1 RETROFIT KIT
    WHY IT WORKS
    RETROFIT COST
    RETROFIT INSTALLATION
    COMPONENT SELECTION
    PRODUCT SOURCES
    CODE COMPLIANCE
    BACKGROUND
  OPTION #2 REPLACEMENT
  OPTION #1 vs OPTION #2
FPE REPLACEMENT PANEL COSTS
CANADIAN VERSIONS
FPE Stab-lok: FIRES WAITING TO HAPPEN
ADVICE TO HOME BUYERS w/ FPE PANELS
HOME INSPECTION LANGUAGE for FPE Stab-Lok
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

RETROFIT INSTALLATION - E-CH Adjustable Retrofit Kit Installation Tips

See the E-CH PDF file (450KB) which explains how this replacement program works. Obtain and follow the installation instructions that come with the equipment. Here are some additional comments:

Distinctive about this approach is that it is not necessary to cut the existing building wall for wire access, and not necessary to disconnect the existing circuits from the original metal panel enclosure "box". Avoiding these steps significantly reduces the labor and installation time.

The Adjustable Retrofit Kit installation procedure is roughly this:

  • select the proper sized load-center that will fit in the existing panel enclosure - measure the existing panel interior dimensions, including depth carefully.
  • if necessary, purchase additional panel enclosure parts such as a frame extension (if the panel Enclosure is too shallow) and a new panel cover front and door may be needed.
  • remove the existing load center (power has been cut off of course). If I were doing it I'd Unscrew each circuit so as to have plenty of length to work with, but most will probably just Cut individual circuit wires close to the old breaker.
  • remove the old load center from the electrical panel
  • cover with metal any improper openings such as knockouts (to assure that the existing enclosure is properly fire resistant
  • mount the new load center
  • connect the existing circuits to breakers in the new load center
  • mount any panel enclosure box extensions (the "picture frame") and electric panel cover
  • Assure the Existing Panel Enclosure is Sound: before ordering the CH Replacement Load Center and Electrical Panel Enclosure Adapter parts, the electrical contractor should take a careful, honest, look at the existing enclosure. If it is not structurally sound don't use the retrofit kit. Some of those older enclosures are 50+ years old, rusted, bent up etc. In that case pull it out and start over. These kits are designed and intended to be used in good, safe, sound enclosures. [See More Reading below.'
  • Cover Openings in the existing panel enclosure (which is to be re-used). Any existing unused holes should be covered. On the smaller holes, this can usually be accomplished by inserting a pan head sheet metal screw of appropriate size to cover the hole. Any unused open knockouts in an enclosure should always be appropriately plugged whether it's a retrofit, repair, new installation etc.
  • Measure carefully: before ordering the particular retrofit enclosure parts, including the depth of the existing panel enclosure, so that the correct retrofit can be supplied.
  • Existing studs or other protrusions: if in the (to be re-used) panel enclosure there are existing studs in the old enclosure that are in the way these will have to be cut off and removed.
  • Flush Mount vs. Surface Mount: These are intended as a "flush mount" application. While they could be used as a "surface mount" the "picture frame" which acts as the adapter collar will extend past the edges of the existing enclosure and may not give a "finished" appearance. This may or may not be of consequence to the owner.

THE FPE Stab-Lok WEBSITE
SUMMARY OF the FPE Stab-Lok PROBLEM
FPE HAZARD ARTICLES, STUDIES
FPE Stab-Lok TECHNICAL REPORT
HOW TO IDENTIFY FPE & FP
REPORTS OF FPE FAILURES
HOW TO REPORT FPE INCIDENTS
FPE REPAIR ELECTRICIANS
FPE REPLACEMENT BREAKERS
REPLACEMENT PANELS
  OPTION #1 RETROFIT KIT
    WHY IT WORKS
    RETROFIT COST
    RETROFIT INSTALLATION
    COMPONENT SELECTION
    PRODUCT SOURCES
    CODE COMPLIANCE
    BACKGROUND
  OPTION #2 REPLACEMENT
  OPTION #1 vs OPTION #2
FPE REPLACEMENT PANEL COSTS
CANADIAN VERSIONS
FPE Stab-lok: FIRES WAITING TO HAPPEN
ADVICE TO HOME BUYERS w/ FPE PANELS
HOME INSPECTION LANGUAGE for FPE Stab-Lok
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

COMPONENT SELECTION - Selecting the Proper Retrofit Kit Components

By following the "Retro Size Grid" on page 5 of the PDF file (450KB), in combination with the selection charts on the following pages, it can be determined just what exactly can be installed in which size enclosure and meet NEC requirements, wire bend etc.

The charts in the PDF (450KB) detail the most common devices asked for and explain the bus amperage rating, number of circuits, and wire size restrictions for minimum enclosure sizes. However since we can not possibly foresee all of the combinations, we have included our 800# to help explain or offer guidance when needed for those who are not sure or have questions or concerns.

The one thing stress by CH is that these are guidelines to meet the minimum requirements per National Electrical Code. Eaton Corp., Cutler Hammer Products cannot assume responsibility for these units when they are not sized or installed correctly.

All final decisions are the responsibility of the AHJ. To date, with 2 years experience, we have had no issues with any AHJ when these are properly installed.

More Reading:
Rust and Corrosion in Electrical Panels, A Study and Report on Frequency and Cause for Electrical and Home Inspectors at Residential Electric Panels


THE FPE Stab-Lok WEBSITE
SUMMARY OF the FPE Stab-Lok PROBLEM
FPE HAZARD ARTICLES, STUDIES
FPE Stab-Lok TECHNICAL REPORT
HOW TO IDENTIFY FPE & FP
REPORTS OF FPE FAILURES
HOW TO REPORT FPE INCIDENTS
FPE REPAIR ELECTRICIANS
FPE REPLACEMENT BREAKERS
REPLACEMENT PANELS
  OPTION #1 RETROFIT KIT
    WHY IT WORKS
    RETROFIT COST
    RETROFIT INSTALLATION
    COMPONENT SELECTION
    PRODUCT SOURCES
    CODE COMPLIANCE
    BACKGROUND
  OPTION #2 REPLACEMENT
  OPTION #1 vs OPTION #2
FPE REPLACEMENT PANEL COSTS
CANADIAN VERSIONS
FPE Stab-lok: FIRES WAITING TO HAPPEN
ADVICE TO HOME BUYERS w/ FPE PANELS
HOME INSPECTION LANGUAGE for FPE Stab-Lok
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

PRODUCT SOURCES - Sources for Adjustable Retrofit Kit for Federal Pacific Electric Panels

Eaton Corp., Cutler Hammer Products Adjustable Retrofit Kits, E-CH Load Centers and load center parts can be purchased through any E-CH distributor.

If your electrician reports that local electrical suppliers are having difficulty finding or specifying kits any of the CH sales force can help. If that effort is not satisfactory contact CH directly at 800-330-6479 or by EMAIL to FlexCenterLincoln@eaton.com.

Other electrical panels: if you are not taking the retrofit kit route (see OPTION #1 vs OPTION #2) then a wide range of electrical panels are available from electrical suppliers and building supply sources.


THE FPE Stab-Lok WEBSITE
SUMMARY OF the FPE Stab-Lok PROBLEM
FPE HAZARD ARTICLES, STUDIES
FPE Stab-Lok TECHNICAL REPORT
HOW TO IDENTIFY FPE & FP
REPORTS OF FPE FAILURES
HOW TO REPORT FPE INCIDENTS
FPE REPAIR ELECTRICIANS
FPE REPLACEMENT BREAKERS
REPLACEMENT PANELS
  OPTION #1 RETROFIT KIT
    WHY IT WORKS
    RETROFIT COST
    RETROFIT INSTALLATION
    COMPONENT SELECTION
    PRODUCT SOURCES
    CODE COMPLIANCE
    BACKGROUND
  OPTION #2 REPLACEMENT
  OPTION #1 vs OPTION #2
FPE REPLACEMENT PANEL COSTS
CANADIAN VERSIONS
FPE Stab-lok: FIRES WAITING TO HAPPEN
ADVICE TO HOME BUYERS w/ FPE PANELS
HOME INSPECTION LANGUAGE for FPE Stab-Lok
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

CODE COMPLIANCE - Code and Legal Acceptance of the Replacement Load Center and CH Adjustable Retrofit Kit

I have corresponded with the lead design engineer for Eaton Corp., Cutler Hammer Products, the company that produces these Replacement load centers. He said that all interiors, neutrals & grounds are their standard UR listed OEM interior components and carry a UR label.

  • UL-Listed The products are all UL Listed. The individual internal components are UR listed and the trim/cover is UL listed as a cabinet front.
  • Code authority accepted: CH have had no code authority refusals
  • Field installations: CH has sold these products in large numbers, sometimes in the thousands to public housing authorities.

Local code approval: Readers should review the CH product specifications and listing information with their electrician and with local code enforcement officials. As with any electrical work, independent inspection and approval of the work is recommended and is required in many jurisdictions. As CH informed me: As we have no control over how /where these are installed, we don't have a "file" we can list these under. Individual OEMs that use many of these on a repeat basis actually get a UL listing on their own device. This is where CH relies on the local inspectors or AHJ to make sure that electricians are installing these products in a safe, and professional manner.


THE FPE Stab-Lok WEBSITE
SUMMARY OF the FPE Stab-Lok PROBLEM
FPE HAZARD ARTICLES, STUDIES
FPE Stab-Lok TECHNICAL REPORT
HOW TO IDENTIFY FPE & FP
REPORTS OF FPE FAILURES
HOW TO REPORT FPE INCIDENTS
FPE REPAIR ELECTRICIANS
FPE REPLACEMENT BREAKERS
REPLACEMENT PANELS
  OPTION #1 RETROFIT KIT
    WHY IT WORKS
    RETROFIT COST
    RETROFIT INSTALLATION
    COMPONENT SELECTION
    PRODUCT SOURCES
    CODE COMPLIANCE
    BACKGROUND
  OPTION #2 REPLACEMENT
  OPTION #1 vs OPTION #2
FPE REPLACEMENT PANEL COSTS
CANADIAN VERSIONS
FPE Stab-lok: FIRES WAITING TO HAPPEN
ADVICE TO HOME BUYERS w/ FPE PANELS
HOME INSPECTION LANGUAGE for FPE Stab-Lok
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

BACKGROUND - Eaton Corp., Cutler Hammer Products' Adjustable Electric Panel Retrofit Kit Development Background

The E-CH electric panel adjustable retrofit program was begun in response to an overwhelming number of contractors who were buying complete loadcenters (metal enclosure, bus assembly, breakers, neutral and ground bars, etc), removing the interior components, neutrals etc and trying to "cobble" something together with "whatever" cover/trim in order to retrofit a new bus assembly into an existing, already mounted electrical panel.

The manufacturer reports that often they saw electric panel interiors shimmed with an unbelievable assortment of items, covers that were questionably attached and in general a "less than professional" final job. Early on it was discovered that there is a tremendous assortment of old electrical enclosures in the field. These old enclosures vary greatly in size (width, length & depth) and in how they were originally installed.

In response to those problems E-CH patented the "Adjustable Retrofit Kit".


THE FPE Stab-Lok WEBSITE
SUMMARY OF the FPE Stab-Lok PROBLEM
FPE HAZARD ARTICLES, STUDIES
FPE Stab-Lok TECHNICAL REPORT
HOW TO IDENTIFY FPE & FP
REPORTS OF FPE FAILURES
HOW TO REPORT FPE INCIDENTS
FPE REPAIR ELECTRICIANS
FPE REPLACEMENT BREAKERS
REPLACEMENT PANELS
  OPTION #1 RETROFIT KIT
  OPTION #2 REPLACEMENT
    REPLACEMENT COST
  OPTION #1 vs OPTION #2
FPE REPLACEMENT PANEL COSTS
CANADIAN VERSIONS
FPE Stab-lok: FIRES WAITING TO HAPPEN
ADVICE TO HOME BUYERS w/ FPE PANELS
HOME INSPECTION LANGUAGE for FPE Stab-Lok
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

OPTION #2 REPLACEMENT - Complete Replacement of the Federal Pacific Electric Panel - Option #2 Conventional R & R Method

Traditional Electric Panel Replacement by Complete Removal of Old Equipment

The traditional and conventional method of replacement of an obsolete (or in this case unsafe) electrical panel has been to completely remove the complete original electrical panel by disconnecting all wires from their individual circuit breakers, disconnect every strain relief, pull the wires out of the panel enclosure, and then to remove the entire electrical panel, enclosure and all.

The new electrical panel is then mounted in place and all of the existing wires are routed back into the new panel, strain reliefs secured, and wires routed to breakers in the new panel. (See "Short wire problem" below).

If the panel being replaced has been mounted on a finished wall (such as behind drywall or paneling) additional labor and disruption are necessary to provide access for wiring and panel mounting.

Electrical Panel REPLACEMENT COST Typical cost of the traditional FPE Electrical Panel Replacement

A number of factors affect the actual cost of replacing an electrical panel, including base labor cost variations in different geographic areas, costs of electrical permits, and the specifics of a particular installation: working space, wire lengths, condition of old wiring, and other factors.

In order to more easily add electrical cost updates in one place, our section on typical costs to replace an electrical panel have been moved to a separate web page. Please see
REPLACEMENT PANEL COSTS

Links on that page will easily permit you to continue reading this article.


THE FPE Stab-Lok WEBSITE
SUMMARY OF the FPE Stab-Lok PROBLEM
FPE HAZARD ARTICLES, STUDIES
FPE Stab-Lok TECHNICAL REPORT
HOW TO IDENTIFY FPE & FP
REPORTS OF FPE FAILURES
HOW TO REPORT FPE INCIDENTS
FPE REPAIR ELECTRICIANS
FPE REPLACEMENT BREAKERS
REPLACEMENT PANELS
  OPTION #1 RETROFIT KIT
  OPTION #2 REPLACEMENT
  OPTION #1 vs OPTION #2
FPE REPLACEMENT PANEL COSTS
CANADIAN VERSIONS
FPE Stab-lok: FIRES WAITING TO HAPPEN
ADVICE TO HOME BUYERS w/ FPE PANELS
HOME INSPECTION LANGUAGE for FPE Stab-Lok
More Information

InspectAPedia TM Home & Site Map
Electrical
Contact Us

OPTION #1 vs OPTION #2 - Comparing Federal Pacific Electric Panel Replacement by Use of the CH Adjustable Retrofit Kit vs. FPE Complete Panel and Enclosure Replacement

WHEN TO USE OPTION#2 - When replacing an FPE Electric Panel When Should the Entire Panel and Enclosure be Replaced?

Using the Retrofit Kit is not appropriate, and complete electrical panel removal and replacement, including the panel enclosure or "box" is going to be necessary when:

  • The existing panel enclosure is not structurally sound, such as if it has become badly rusted.
  • The building needs a larger ampacity service, say moving from 100A to 200A at a building, and the building needs more electrical distribution circuits than what are presently installed. In this case it is likely that even if a new bus assembly that could handle the higher ampacity of a new service it will not handle the needed number of circuit breakers. The installer may consider a retrofit anyway, using a circuit in the retrofit panel to feed a new subpanel which is located elsewhere in the building and which provides additional circuits. That approach may suit where the added circuits and ampacity are in support of a building addition such as a new wing or level.
  • The area where the panel is located is being gutted and re-modeled in concert with installing a new larger panel, service, ampacity, and number of circuits.
  • The electric panel is not built into a finished wall (for example exposed in a basement or garage), so that all of the panel's exterior is readily accessible, and the panel capacity is not being upgraded. In this case I'd do a cost comparison of all of the retrofit equipment needed vs. the whole new box approach. CH believes that even in this case the retrofit approach might be less costly.
  • The electrical panel needs to be relocated for other reasons.

More Reading:
Rust and Corrosion in Electrical Panels, A Study and Report on Frequency and Cause for Electrical and Home Inspectors at Residential Electric Panels

Comparing the Two Electric Panel Options: #1-Adjustable Retrofit Kit or #2-Complete R&R Replacement of Everything

[Opinion offered by the web author]

  • Cost: Option #2, Federal Pacific Electric Panel removal and replacement with a new Brand-x electrical panel is likely to cost twice as much as Option #1 with the CH Replacement Load Center and Electrical Panel Enclosure Adapter.
  • Time: Option #2 can be expected to require at least twice the labor of Option #1.
  • Disruption: When the original Federal Pacific Panel is installed in a finished wall, Option #2 requires partial demolition for working space that should not be necessary for Option #1
  • Availability: Option #2 permits choice of any manufacturer's electrical equipment; Option #1 is available only from Eaton Corp., Cutler Hammer Products. This is a widely distributed brand but may not be stocked at the same levels as products by other manufacturers. Additional delay may be encountered if your electrician's electrical supply house has to order the CH Panel Enclosure Adapter parts. I will report here what readers encounter - feedback is invited.
  • Suitability: Option #2 is required when the original panel enclosure is damaged or for other reasons I listed earlier. Option #1 is not suitable in those cases.

Where Option #1 is suitable it strikes me as appealing for reasons of cost and trouble.

When performing a conventional electrical panel replacement, in order to have adequate wire length to connect things in the new electrical panel the electrician would have to not only disconnect or clip wires at each breaker, s/he would also have to unscrew every strain relief and pull each individual wire out of the existing panel enclosure - a crowded and tedious operation that has to be done with great care so as not to damage the insulating jacket on the existing wires. This has to take considerably more time than just replacing the load center in the existing panel enclosure where all of the wires entering the original box can be left in place.

There is no cosmetic damage to the wall where the existing panel is mounted when using Option #1. By comparison, with an conventional electrical panel replacement if the panel is in a finished area, the electrician has to cut away the finished wall surface to have access to the individual wire strain reliefs entering the panel box in order to disconnect them, and also in order to have working room to get the new wires into the new electrical panel enclosure. Further, it is unlikely that a new panel enclosure will have the same dimensions or "footprint" as the old, possibly meaning additional adjustments at the finish wall.

Many people have contacted me to ask advice about FPE electric panel replacement options. More than I am able to answer by telephone or even email. Both for individual home owners and especially for larger buildings or building complexes where there are many, sometimes hundreds of FPE Stab-Lok electric panels installed, the cost of a complete gut-out replacement of the panel is a significant burden. If this sounds as if I'm writing a commercial, that's not my intention, and I have no connection with the manufacturer of this product nor any financial interest in it nor in any other products discussed at this website.

I am afraid that the cost of complete electrical panel replacement has been a factor in moving some owners to try to just "replace the FPE circuit breakers themselves" with the mistaken notion that somehow this reduces their risk of a fire. Unfortunately it does not appear to do so. I have found no data suggesting that replacement FPE breakers perform any better than their predecessors in the U.S. and probably not in Canada.

Even if a new perfectly reliable circuit breaker were built to fit these panels, underlying problems with the FPE bus design, breaker to bus connections, and bus overheating and failures would remain. This is why I continue to recommend a complete panel replacement for these problem brands.

I also have received reports of reluctance to report the hazards with this equipment, either because of the conflicting interests surrounding pre purchase home inspections or in one instance a correspondent was afraid of losing his/her job by reporting a costly problem at a multi-building complex where many problem panels were installed.


Technical Reviewers

Particular thanks are due to experts and also consumers who read these articles and suggest corrections, changes, and additions to the material. Content suggestions, technical corrections and content critique are invited for any of the content at our website.

  • Daniel Friedman - principal author/editor of the InspectAPedia © Website
  • Thanks to Lance Caddell, Master Electrician, Caddell Electric, LLC. for comments and corrections 2/16/08
  • Critique, contributions wanted: Contact Us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.

Information Source Citations & Feedback Request

Information Source Notice: portions of the text of this document are from email exchanged between the web author and the Eaton Corp., Cutler Hammer Products Lead Design Engineer and Eaton Product Manager involved with the products discussed in this document. The illustration at page top is from the Eaton Electrical PDF which describes their product line. The author has no financial nor any other connection with Eaton Corp., Cutler Hammer Products, nor any other company whose products are discussed at this website. Corrections of errors or omissions, product user feedback, or other critique are invited. Our editorial policies are at Accuracy & Bias Pledge

I'd welcome some photos and description of field experience from installing electricians and from consumers. Contact Us to report field experience with this equipment.

Use links at the left of each page to navigate this document or to view other topics at this website. Green links at page left show where you are in our document or website.




THE FPE Stab-Lok WEBSITE
SUMMARY OF the FPE Stab-Lok PROBLEM
FPE HAZARD ARTICLES, STUDIES
FPE Stab-Lok TECHNICAL REPORT
HOW TO IDENTIFY FPE & FP
REPORTS OF FPE FAILURES
HOW TO REPORT FPE INCIDENTS
FPE REPAIR ELECTRICIANS
FPE REPLACEMENT BREAKERS
FPE REPLACEMENT PANELS
FPE REPLACEMENT PANEL COSTS
CANADIAN VERSIONS
FPE Stab-lok: FIRES WAITING TO HAPPEN
ADVICE TO HOME BUYERS w/ FPE PANELS
HOME INSPECTION LANGUAGE for FPE Stab-Lok

More Information

InspectAPedia TM Home & Site Map
Air Conditioning
InspectAPedia Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Bias Pledge
InspectAPedia TM Home & Site Map
Contact Us

More Information about FPE Federal Pacific Stab Lok Panels and Circuit Breakers - Reference List

goto InspectAPedia.com - authoritative, in-depth Building Diagnostic and Repair Information for building buyers, owners, inspectorsInspectAPedia TM Home & Site Map - Building Inspection, Diagnosis, & Repair, Environmental Inspection & Testing - Research Website

GO TO our PRE PURCHASE BUILDING INSPECTION SERVICES: Authoritative information for home buyers and home owners is included with your inspection.Home Inspection Construction Consulting Services & advice for home buyers

CONTACT Daniel Friedman - Dan is a senior ASHI home inspector, nationally recognized expert on building inspection, building failures, and sick building investigationContact Daniel Friedman for website content suggestions or for fee-paid consulting

Google
 
Advertise on This Website →

02/16/2008 - 06/03/06 www.inspect-ny.com/fpe/fpereplace.htm © 2008-1986 Daniel Friedman - All Rights Reserved