Mobile View
HEATING SYSTEMS
ANTI SCALD VALVES
BOILERS, HEATING
BOILER OPERATION DETAILS
BOILER CONTROLS & SWITCHES
Air Bleeder Valves
Aquastat Functions
BOILER LEAKS CORROSION STAINS
BOILER OPERATING PROBLEMS
BOILER PARTS LIST
Cad Cell Relay Switch Flame Sensors
Circulator Pumps & Relays
Expansion Tanks
Gauges on Heating Equipment
Limit Switches, Boilers
Low Water Cutoff Valves, Boilers
Mixing Valves
Relief Valves - TP Valves
Spill Switches
Stack Relay Switch
Zone Valves
CARBON MONOXIDE/DIOXIDE
CARBON MONOXIDE WARNING
CHIMNEY INSPECTIONS
CHIMNEYS & Flues - Asbestos Transite Pipe
DRAFT HOODS - gas fired
DRAFT REGULATORS - barometric dampers
DUCT SYSTEMS
DUCT INSULATION, Asbestos Paper
DUCTS, Asbestos Transite Pipe
DUST FROM HVAC?
ELECTRICAL POWER SWITCH FOR HEAT
FURNACES, HEATING
DUCT SYSTEM DEFECTS
FAN LIMIT SWITCH
FURNACE CONTROLS & SWITCHES
FURNACE OPERATION DETAILS
HEAT EXCHANGER LEAKS
STACK RELAY SWITCHES
GAS PIPING, VALVES, CONTROLS
GAUGES ON HEATING EQUIPMENT
HEAT LOSS INDICATORS
HEATING COST SAVINGS
HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES
HEATING OIL CLOUD WAX GEL POINT
HEATING OIL SLUDGE
HEATING SYSTEM INSPECTION DIAGNOSIS REPAIR
HEATING INSPECTION CONCEPTS
HEATING INSPECTION PROCEDURE
HOT WATER IMPROVEMENT
INSULATION
MIXING VALVES
NO HEAT - BOILER / FURNACE DIAGNOSIS
OIL BURNERS
OIL BURNER NOISE SMOKE ODORS
OIL FUEL TYPES & CHARACTERISTICS
OIL TANK LEAKS
OIL TANK SLUDGE
OIL TANKS, BURIED
PLASTIC HEATER VENT
RADIANT HEAT Floor Mistakes to Avoid
RELIEF VALVES - TP Valves
Safety Recalls
BLUERAY Recall
CHIMNEYS & Flues - Asbestos Transite
Goodman HTPV RECALL
Lennox WARNING
Weil McLain RECALL
SAFETY DURING HEATING INSPECTION
SPILL SWITCHES - Flue Gas Detection
STAIN DIAGNOSIS on Indoor Surfaces STEAM HEATING SYSTEMS
Cad Cell Relay Switch Flame Sensors
Low Water Cutoff Valves, Boilers
Mixing Valves
Relief Valves - TP Valves
Sight Glass, Steam Boiler
Pressure Switch, Steam Boiler
Spill Switches
Stack Relay Switch
Steam Vents
LOW WATER CUTOFF CONTROLS
WATER FEEDER VALVES, STEAM
TANKLESS COILS
Tankless Coil Leaks
THERMAL TRACKING
THERMOSTATS
Transite Pipe Chimneys & Flues
ZONE VALVES
More Information
InspectAPedia TM Home & Site Map
Air Conditioning
InspectAPedia Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Bias Pledge
Contact Us
|
Guide to Heating System Circulator Pumps & Circulator Relays
HeatAPedia ©
- Circulator Pumps: Hot Water Heating System Circulator Troubleshooting & Repair Guide
- Circulator pump relay switches & controls on heating systems: Troubleshooting & Repair Guide
- Troubleshooting heating system boiler controls and switches
Our site offers impartial, unbiased advice without conflicts of interest.
We will block advertisements which we discover or readers inform us are associated with bad business practices,
false-advertising, or junk science. Our contact info is at
inspect-ny.com/appointment.htm.
Here we discuss Circulator Pumps: how to find, inspect, diagnose, and repair problems with Hot Water Heating System Circulator Pumps
or circulator pump relay switches and controls. Also you will see that
this website answers most questions about Heating System Boiler Controls on central heating systems to aid in troubleshooting, inspection, diagnosis, and repairs.
Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.
© Copyright 2008 Daniel Friedman, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use links at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.
The circulator pump, such as the trio of pumps shown at the top of this page, is used to move hot water from the heating boiler out through
one or more loops of piping in a building, through heating devices such as radiators, heating baseboards, or convector units, then
through return piping back to the heating boiler. When the water temperature drops to a pre-set level the heating boiler will re-heat
the water.
The circulator relay is an electrical switch which, in response to a request for heat from a thermostat, turns on the circulator pump.
Some heating systems use a single circulator to move hot water through the building's heating devices. In a one-circulator system, the
building may still divide its heat into various zones or sub-areas of individual heat control, by using either individual radiators in
rooms or perhaps by using electrically controlled zone valves which open and close flow of hot water through sub-loops in the building
heating piping.
Some heating systems use multiple circulators to provide heat to individual building areas or "zones". In this case each heating zone
will have its own thermostat which, acting as a low-voltage "heat on-off switch" will turn on individual circulator pumps when heat is
desired in that zone.
Less common are mixed heating zone systems in which multiple circulators are used but one or more of the circulators feeds a heating
water pipe which is subsequently divided into additional sub-zones of heat control, each sub-zone being controlled by a zone valve.
Which is better: heating control using zone valves or heating control using individual circulators?
Either approach to individual heating zone control can work just fine - using zone valves or using individual circulators.
Some heating contractors prefer using individual circulator pumps, one per zone, perhaps because they recall the history of
unreliable zone valves which tended to clog or jam in some models by some manufacturers. The "zone valve" fellows retort that
modern heating zone valves are as reliable or more reliable than [some models of] heating circulator pumps and that a zone
valve costs a lot less.
Adding zone control to an existing heating system may be less costly by adding a zone valve than by adding a circulator pump.
What goes wrong with hot water heating circulator pumps and circulator switches
How to tell if the circulator pump is working - some circulators are quiet - which pipes to feel
Leaks at heating circulator pumps: where leaks most often occur (circulator pump mounting flanges)
Bearing and motor failures on circulator pumps and what causes them: circulator pump mounting and support errors
[Text under revision 12/24/2007 - to be posted January 2008]
- Individual High Limit and Low Limit relay switches on heating boilers: these may be provided on older heating boilers.
- Zone valves on heating boilers - heating water piping in a building, particularly where hot water baseboard heat is used, may be divided into separate heating zones (different floors, or different areas on a single floor) to
permit more detailed control of heat distribution in a building. The control of heating water through these different heating zones may be accomplished
by use of zone valves (one per heating zone or area or "loop" of heating piping) which in turn are connected to individual thermostats. When the thermostat
calls for heat in a particular building area, the thermostat switch causes the zone valve to open, to permit hot water to flow through that zone.
When the zone valve is fully open, an "end switch" inside the valve tells the heating system's circulator to begin operating, causing hot water to flow
through the zone. Typically heating systems using zone valves will have two or more zone valves (usually but not always located close to the heating
boiler) and a single circulator pump (usually located on the return end of the hot water piping close to the heating boiler).
- Circulator relays on heating boilers - an older and by some heating service technicians, a preferred method to control the distribution of heat to individual
building areas uses a individual circulator pump to force heating water through each individual heating zone piping. This system too is usually found
on hot water baseboard heating systems. Two or more circulator relay switches, one relay for each circulator pump, will be installed to turn on and off
each heating water circulator if more than one heating circulator is installed. Individual low-voltage thermostats located in the living area will respond to
a call for heat by switching on the circulator relay which in turns on the (120V) circulator pump.
Technical Reviewers
Particular thanks are due to experts and also consumers who read these articles and suggest corrections, changes, and additions to
the material. Content suggestions, technical corrections and content critique are invited for any of the content at our website.
Use links at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.
More expert information on this topic
|
HEATING SYSTEMS
HEATING SYSTEM INSPECTION DIAGNOSIS REPAIR
More Information
InspectAPedia TM Home & Site Map
Air Conditioning
InspectAPedia Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Bias Pledge
Contact Us
|
More Information on Inspecting and Repairing Heating Systems
- Carbon Dioxide Gas Toxicity
- Carbon Monoxide Gas Toxicity, exposure limits, poisoning symptoms, and inspecting buildings for CO hazards
- Dust from HVAC? An Investigation of Indoor Dust Debris Blamed on a Heating/Cooling System Reveals Carpet Dust
- Goodman Furnace High Temperature Plastic Vent HTPV safety recall US CPSC notice
- Home Heating System Should Be Checked [for proper venting and for CO Carbon Monoxide Hazards - DJF]
- Inspection Procedures for Oil-Fired Heating Systems Detailed step by step approaches for inspecting complex systems]
- Lennox Pulse Furnace Safety Inspection/Warranty Program: Carbon Monoxide Warning
- Oil Tanks - The Oil Storage Tank Information Website: Buried or Above Ground Oil Tank Inspection, Testing, Cleanup, Abandonment of Oil Tanks
- Oil Tanks Above Ground, UL Standards, guidance for home owners, buyers, and inspectors
- Plastic Heating Vent Pipe & Other Heating Safety Recall Notices
- Weil McLain Model GV Gas Boiler/gas valve CPSC recall/repair
- Domestic and Commercial Oil Burners, Charles H. Burkhardt, McGraw Hill Book Company, New York 3rd Ed 1969.
- National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
- The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update,
- Principles of Steam Heating, $13.25 includes postage. Fuel oil & Oil Heat Magazine, 389 Passaic Ave., Fairfield, NJ 07004.
- The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
- Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
- "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
- "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
- "Warm Air Heating Systems". Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
- Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals,
- Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
- Installation Guide for Residential Hydronic Heating Systems
- Installation Guide #200, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922
- The ABC's of Retention Head Oil Burners, National Association of Oil Heat Service Managers, TM 115, National Old Timers' Association of the Energy Industry, PO Box 168, Mineola, NY 11501. (Excellent tips on spotting problems on oil-fired heating equipment. Booklet.)
InspectAPedia TM Home & Site Map - Building Inspection, Diagnosis, & Repair, Environmental Inspection & Testing - Research Website
The Mold Information Center: What to Do About Mold in Buildings, When and How
to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems
Home Inspection Construction Consulting Services & advice for home buyers
Contact Daniel Friedman for website content suggestions or for fee-paid consulting
| Advertise on This Website → |
|
| |