InspectAPedia ®

Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice
InspectAPedia
Home
| Air
Conditioning
| Electrical | Indoor
Environment
| Exteriors | Heating | Home
Inspection
| Insulate
Ventilate
| Interiors | Mold
Inspect/Test
| Plumbing
Water
Septic
| Roofing | Structure | Contact Us
Directory of Professionals to Inspect or Test a Building


Mobile Phone or PDA view of this websiteMobile View
HEATING SYSTEMS
AIR FILTERS for HVAC SYSTEMS
AIRBOUND HEAT SYSTEM REPAIRS
ANODES & DIP TUBES on WATER HEATERS
ANTI SCALD VALVES
BACKFLOW PREVENTERS
BACKUP HEAT for HEAT PUMPS
BAROMETRIC DAMPERS
BLOWER DOORS & AIR INFILTRATION
BLUERAY Recall
BOILERS, HEATING
  BOILER CONTROLS & SWITCHES
  BOILER LEAKS CORROSION STAINS
  BOILER OPERATING PROBLEMS
    Types of Boiler Defects
    Air-bound radiators or piping
    Diagnose Loss of Heat
    Diagnose Oil Heat Noises
    Evaluate Heating Boiler Leaks
    Combustion Air Defects
    Heating Malfunctions & Implications
    Heating Defects & Implications
  BOILER PARTS LIST
  Air Bleeder Valves
  Air Separator Purge Valves
  Aquastat Functions
  Cad Cell Relay Switch Flame Sensors
  Circulator Pumps & Relays
  Draft Regulators, Barometric Dampers
  Expansion Tanks
  Gauges on Heating Equipment
  Limit Switches, Boilers
  Low Water Cutoff Valves, Boilers
  Mixing Valves
  Pressure Gauges, Boilers
  Relief Valves - TP Valves
  Reset Switch - Primary Control
  Reset Switch - electric motors
  Spill Switches
  Stack Relay Switch
  Thermostats
  Water Feeder Valves, Hydronic Boiler
  Zone Valves
BOILER LEAKS CORROSION STAINS
BOILER NOISE SMOKE ODORS
BOILER OPERATING PROBLEMS
BOILER OPERATION DETAILS
BOILER PARTS LIST
CARBON MONOXIDE/DIOXIDE
CARBON MONOXIDE WARNING
CHIMNEY INSPECTION DIAGNOSIS REPAIR
CHIMNEYS & Flues - Asbestos Transite Pipe
COOL OFF HEAT Thermostat Switch
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
DEFINITION of Heating & Cooling Terms
DRAFT HOODS - gas fired
DRAFT REGULATORS, DAMPERS, BOOSTERS
DUCT SYSTEMS
DUST FROM HVAC?
ELECTRIC HEAT
ELECTRICAL POWER SWITCH FOR HEAT
FIREPLACE Damage & Unsafe Hearths - Settlement
FLUE VENT CONNECTORS
FREEZE-PROOF A BUILDING
FURNACES, HEATING
FURNACE CONTROLS & SWITCHES
FURNACE OPERATION DETAILS
GAS PIPING, VALVES, CONTROLS
HEAT EXCHANGER LEAKS
HEAT LOSS in BUILDINGS
HEAT LOSS INDICATORS
HEAT LOSS R U & K VALUE CALCULATION
HOUSEWRAP AIR & VAPOR BARRIERS
HEAT TAPES, Heat, Insulation prevent Freeze-Up
HEATING COST FUEL & BTU Cost Table
HEATING COST SAVINGS METHODS
HEATING LOSS DIAGNOSIS-BOILERS
HEATING LOSS DIAGNOSIS-FURNACES
HEATING OIL CLOUD WAX GEL POINT
HEATING OIL EXPOSURE HAZARDS, LIMITS
HEATING OIL SLUDGE
HEAT PUMPS
HEATING SYSTEM INSPECTION PROCEDURE
HIGH EFFICIENCY BOILERS/FURNACES
INSULATION
MOTOR OVERLOAD RESET SWITCH
NO HEAT - BOILER / FURNACE DIAGNOSIS
ODORS FROM HEATING SYSTEMS
OIL BURNERS
OIL BURNER NOISE SMOKE ODORS
OIL FUEL TYPES & CHARACTERISTICS
Oil Odors: Leaky Oil Tank Piping
OIL TANKS
OIL TANK GAUGES
OIL TANK LEAKS & SMELLS
OIL TANK PIPING DEFECTS
OIL TANK PRESSURE
OIL TANK SLUDGE
OIL TANK TESTING
OIL TANKS, BURIED
PLASTIC HEATER VENT
PULSE COMBUSTION HEATERS
RADIANT HEAT Floor Mistakes to Avoid
RADIATORS
RELIEF VALVES - TP Valves on Boilers
Relief Valves - Water Heaters
SAFETY DURING HEATING INSPECTION
Safety Recalls
  BLUERAY Recall
  CHIMNEYS & Flues - Asbestos Transite
  Goodman HTPV RECALL
  Lennox WARNING
  Weil McLain RECALL
SPILL SWITCHES
STACK RELAY SWITCHES
STEAM HEATING SYSTEMS
  Cad Cell Relay Switch Flame Sensors
  Circulator Pumps & Relays
COMBUSTION GASES & PARTICLE HAZARDS
COMBUSTION PRODUCTS & IAQ
DEFINITION of Heating & Cooling Terms
DRAFT HOODS - gas fired
  DRAFT REGULATORS - barometric dampers
  Expansion Tanks
  Gauges on Heating Equipment
  Limit Switches, Boilers
  Low Water Cutoff Valves, Boilers
  Mixing Valves
  Pressure Switch, Steam Boiler
  Relief Valves - TP Valves
  Sight Glass, Steam Boiler
  Spill Switches
  Stack Relay Switch
  Steam Pressure Gauge
  Steam Vents
  Low Water Cutoff Controls
  Water Feeder Valves, Steam
TANKLESS COILS
THERMAL TRACKING
THERMOSTATS
Transite Pipe Chimneys & Flues
VIDEO GUIDES: Heating System Videos
VIDEO GUIDES - InspectAPedia.com
WATER HEATERS
Water Heater Noises
Water Heater Scale - De-Liming Procedures
WINTERIZE A BUILDING
Wood Burning Heaters Fireplaces Stoves

More Information

InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
Air Conditioning & Heat Pumps
Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Bias Pledge
Contact Us

Photograph of a burning-up and possibly dangerous oil-fired heating boilerHow to Recognize & Diagnose Heating Boiler Problems
HeatAPedia ©

  • How to diagnose loss of heat or no heat
  • Diagnose heating boiler noises, leaks, odors, or smoke
  • Troubleshoot heating boiler oil or gas burners & controls
  • How to inspect & repair central hot water heating boilers - hydronic heating
  • Baseboard, radiator, convector heat inspection, defects, repairs
Our site offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at inspect-ny.com/appointment.htm.

Here we discuss how to recognize & diagnose problems with residential heating boilers, including loss of heat, heating boiler noises, leaks, odors, or smoke, and high heating costs. This website answers most questions about central hot water heating system troubleshooting, inspection, diagnosis, and repairs. If you have no heat and need help diagnosing the cause, see HEATING LOSS DIAGNOSIS-BOILERS or HEATING LOSS DIAGNOSIS-FURNACES. The photograph shows a heating boiler which is burning through it's steel outer jacket - this condition is a potential fire hazard and requires immediate inspection and repair. There is probably a combustion gas leak at this heater. Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution. © Copyright 2009 Daniel Friedman, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use links at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

To Recognize Heating System Defects the Heating System Inspector Must Know the Equipment

If you don't know whether your heat is provided by a furnace (hot air) or boiler (hot water), or whether your fuel is oil, gas, or electric, it will be helpful to first review our descriptions of hot water or "hydronic" heating systems at BOILER COMPONENTS & PARTS and BOILER OPERATION DETAILS which describe hot water heating systems, and also review our descriptions of furnaces and hot air heat at FURNACES, HEATING COMPONENTS

Types of Defects and Problems with Hot Water Heating Boilers - Hydronic Heating Systems, Loss of Heat, Noises, Leaks

What sort of defects should you look for when inspecting a heating system?

  • Unsafe conditions on the heating system such as signs of burn-out of the combustion chamber liner, unsafe relief valves, unsafe flue gas venting, fuel leaks, combustion gas leaks.
  • Loss of heat - boiler or furnace won't operate, or system operates but heat is not produced in the living area - we provide a guide to diagnosing the reasons for "no heat" beginning at NO HEAT - BOILER / FURNACE DIAGNOSIS. If your hot water heating system is running (the steam or hot water boiler is making noise and seems to get hot) but some of your radiators or baseboards are cold, see RADIATORS and AIRBOUND HEAT SYSTEM REPAIRS.
  • Improper Heating System Function: noises, odors, soot, burn marks on the furnace or boiler, unreliability, inadequate heat distribution. Soot production by gas fired heating equipment is an immediate, serious hazard thar risks potentially fatal carbon monoxide poisoning. Turn such equipment off and call for expert advice. Severe smoking and soot puffback from oil fired heating equipment is also dangerous and requires immediate action.
  • Improper heating system maintenance, such as failure to adequately clean and inspect the heating flue, furnace, or boiler, unsafe heating safety devices (e.g. relief valves), evidence of sooty, noisy operation, leaks in fuel, air, water. An example of an easy-to-spot clue that an oil fired heating system needs service and cleaning is illustrated at DRAFT REGULATORS - barometric dampers
  • Improper Heating System Construction/Installation
  • Missing Heating System Components or missing or damaged heater safety controls, operating aids
  • Unreliable heating systems or heating systems at or near the end of their useful life
  • Heating System Damage: leaks, mechanical damage, combustion chamber damage
  • Oil Burner Noise, Smoke, Soot, Odors - Diagnosis & Cure
  • Clues of potential other heating system defects: leaks, corrosion, stains, abnormal temperature or pressure, high heating fuel bills

How to Diagnose Loss of Heat With Oil-Fired Hot Water Heating Systems

  • Does the heating equipment have electric power?: make sure that electrical power is on for all of the heating system components. Check local switches at the boiler, wall mounted boiler switches at the stairwell down to the basement or utility room or in other areas, and check the circuit breakers or fuses in the electrical panel.
  • Is there fuel for the boiler ?: check the oil tank gauge; if the boiler or furnace is fired by natural or LP gas check that no one has shut the supply valves. If a system has been "shut down" and you don't know when or by whom this step was taken, beware of turning the heating system back on without an inspection and safety check by an expert technician. If you're out of oil call your oil company and request an emergency delivery. Usually the delivery person will also need to enter the building to bleed air from the oil lines in order to get the oil urner operating again.
  • Does the oil burner start but then shut off? Is the system "off on reset"? if so the red "reset" button will have popped up on the oil burner control (or possibly on an electric motor operating the oil burner) and the system has an operating problem and needs service. It may be possible to re-start an oil burner that has turned itself off by pressing the red reset button ONCE. If the system re-starts and runs acceptably, you can have heat while waiting for the service technician but the system still needs inspection, service, and possibly other repairs before it can operate safely and reliably. If you push the reset button and the burner does not start and keep runnign for five minutes or more, DO NOT try again as you may flood the system with oil and make restarting difficult and dangerous.
  • Boilers-Hydronic Heat: Is hot water water circulating?
    • Check the hot water circulator: Test to see if the circulator is operating Feeling the hot water distribution piping (Watch out it should be HOT!). Feeling the piping can indicate if circulator is running or not -- a quick change in temperature means the circulator works; slow change in temperature may occur if the circulator does not work but hot water is circulating by convection.
    • Check hot water baseboards: if some baseboards are hot and others cold, are they all on the same heating zone? If not, are all of the thermostats turned up? If some heating baseboards are hot and others cold and we're sure that they're on the same zone, then the system is probably air-blocked.

      A heating circulator pump is capable of pushing water around in the loop of heating baseboard but is often not capable of overcoming a section of baseboard that contains a large bubble of air. It's necessary to remove such air blocks. If air blocking has been recurrent a previous owner may have installed air bleeders at strategic points.

      The bleeder can be opened slightly and carefully, to permit air to escape. As soon as water starts coming out of an air bleeder valve it can be closed. Automatic air purge devices are available and are usually installed right at the heating boiler but sometimes additional ones are needed at higher levels in the building.
    • Check hot water radiators or convectors: if some radiators or wall convectors are hot and others are cold, and provided that the individual feed valves located at each of these devices is open (turned counterclockwise) the radiator or convector may be air blocked. Usually an individual air bleed valve is located on each of these devices. As we suggested above, if your hot water heating system is running (the steam or hot water boiler is making noise and seems to get hot) but some of your radiators or baseboards are cold, see RADIATORS and AIRBOUND HEAT SYSTEM REPAIRS.

How to Diagnose Noises during Heating System & Oil Burner Operation

  • Noises during oil burner startup - a "bang" or "puffback" which blows soot into the room through the barometric damper or through other equipment openings: the oil pump may not be shutting down properly at the end of an oil burn cycle, leaking incompletely burned oil into the combustion chamber. That oil ignites at startup causing a potentially dangerous puffback. Immediate service and repair are needed.
  • Noises during oil burner startup - a "rumbling" sound (which usually continues all during operation" or a "stumbilng" sound in the combustion chamber probably indicates that the system needs inspection and cleaning very soon. Some noise is normal however, but the normal sounds tend to be more smooth and continuous.
  • Noises during oil burner shut-down - a stumbling or rumbling after the oil burner motor has stopped, indicate that oil is continuing to leak into the combustion chamber and risks a dangerous puffback - see "Noises during oil burner startup" above. Immediate service is recommended.
  • Noises of shrieks or grinding coming from the electric motor or oil pump on the oil burner mean that immediate service is needed - probably a bearing is failing.
  • Startup problems: noises and clues of puff back: if you see flapping at the barometric damper or if you see or hear vibrations in the system, prompt service is needed
  • Noises from radiators or heating baseboards:
    • Clanking heating pipes or sharp snapping noises may be heard as a normal consequence of expansion of metals during the heating cycle. These noises can often be eliminated or reduced by careful routing of piping and by allowing room around heating pipes for expansion, but probably not elminated in the case of hot water baseboards.
    • Bubbling or rumbling noises in hot water heating piping can be caused by air in the heating lines. If the amount of air becomes excessive the system may be unable to circulate hot water and extra steps to bleed unwanted air will be required.
    • Hissing sounds such as air escaping from radiators or othe piping where air bleeder valves are installed are normal but should be brief and uncommon. If you constantly hear air hissing from radiator bleed valves double check that you understand what kind of heat you have - hissing from bleeder valves on steam heat radiators as heat is coming up in the building is normal.

How to Evaluate Heating Boiler Leaks & Corrosion

When observing evidence of leaks on a heating boiler, keep these points in mind:

  • Even serious leaks may never show up as "wet" spots: A boiler may be leaking but you may see no actual water: during the heating season the boiler may always be hot, causing small leaks on the boiler or on heating piping to simply evaporate. But such leaks will usually be visually very evident: look for a build-up of corrosion, green or white or other colored mineral salts, or look for rust or water stains on the equipment.
  • Internal heating boiler leaks: Some critical boiler leaks may be internal and not visible by simple inspection, such as a leak inside the boiler heat exchanger which may pass water into the combustion chamber. A service technician or a skilled home inspector should be able to spot evidence of these leaks.
  • Surface rust, light, superficial rusting, is generally repairable. Clean the area and fix the leak when the boiler is next serviced and monitor for any future leaks.
  • Exfoliation, or thick flaking rust on any boiler but particularly on a steel heating boiler is very serious, possibly not repairable, and risks loss of the boiler as well as sudden loss of heat in the building.
  • Leaks related to temperature or pressure: Some leaks occur only at peak operating temperature--eg at relief valve. On some heating boilers such as some cast-iron units, leaks may occur between boiler sections when the system is cold - on these models some technicians prefer to keep a little heat in the boiler year-round to avoid this problem. Leaks between boiler sections may be repairable but if left unattended can destroy the equipment.

A Catalog of Common Heating System Leak Points - Where to Watch for Heating System Leaks

  • Tankless Coil mounting plate - see rust stains below and around plate
  • Pipe fittings at face of coil plate - mineral salts
  • Leaks around bolt openings - suspect hidden damage
  • Leaks between sections of a cast iron boiler
  • Leaks at the circulating pump mounting flanges
  • Leaks at the boiler temperature/pressure relief valve. This leak may be very dangerous as corrosion from water passing through the valve may prevent its safe operation in an emergency. Prompt expert inspection and repair are needed. Watch for leaks below the valve's mouth or discharge pipe (a pipe should extend from the relief valve to a few inches from the floor) or watch for corrosion at the tip of the discharge pipe. Gently feel inside the tip of this pipe to see if it's wet. DO NOT TRY TO TEST or open or operate the relief valve itself.
  • Leaks at air bleeder valves - at the boiler or remote where such bleeders are placed on heating piping or baseboards or radiators
  • Leaks at radiator control valves
  • Leaks at poorly-soldered copper pipe fittings on finned copper baseboard heating systems
  • Leaks due to frozen and burst piping or in extreme cases, frozen and burst heating boilers themselves

How to Recognize & Diagnose Inadequate Combustion Air, Sooting, or Burn Marks at Oil-Fired Heating Systems

Backpressure sooting at an oil fired furnace (C) Daniel FriedmanBackpressure Burn at an oil burner (C) Daniel Friedman

Lack of adequate combustion air can be indicated by or can result in these heating system operating and safety worries:

  • Improper oil burner system operation such as noises, rumbling, etc. discussed above
  • Oil burner sooting or dirty operation (the photo at above-left)
  • Burn marks on the boiler (photo at above right), furnace, or water heater, (these conditions may be caused by a blocked exhaust flue and inadequate venting).

    Safety warning: burn marks on a heating boiler or furnace (shown in our page top photo) can also be due to collapse or damage to the combustion chamber liner - a serious fire hazard needing immediate attention. Notice that in our photo at right, the brown burn marks around the oil boiler combustion chamber inspection port (that rusty round door above the oil burner) have been cleaned-off.

    The presence of these burn marks does not necessarily mean that the oil burner backpressure problem remains - in this case the system has been cleaned and adjusted, but no one has re-painted the front of the boiler. But if you see fresh peeling paint or soot in such an area further investigation is needed.

    That's why we recommend that after repairing a back-pressure problem at heating equipment the service technician should clean the boiler or furnace exterior - to remove confusing debris and to make it easier to see if the problem recurs.
  • Heating equipment located in a small utility room with no provision for combustion air intake. When the service technician adjusts the system she probably worked with the utility room door open, but when the service tech left the job he may have closed the door - completely changing the availability of combustion air for the equipment. We need about one square inch of un-louvered (unobstructed) combustion air intake per 1000 btuh of the oil fired heating boiler, furnace, or water heater.
  • Increased heating system operating cost,
  • damage to oil burner components (backpressure heat can destroy an ignition transformer),
  • higher and more frequent heating service costs,
  • loss of heat,
  • Noises when the boiler, furnace, or water heater starts, is operating, or is shutting down
  • Smoke indoors,coming out of the heating equipment or its draft regulator
  • potentially, the production of carbon monoxide or other flue or combustion gases which escape into the building - potentially dangerous

Also see Unsafe Air Conditioning or Heating Duct Openings which describes the risks of reduced combustion air on hot air heating systems when certain return air duct defects are present, and also see CARBON MONOXIDE/DIOXIDE and CHIMNEY INSPECTION DIAGNOSIS REPAIR

A Guide to Heating Equipment Malfunctions & Their Implications

  • Noises & soot buildup can lead to a potentially dangerous "puffback" which can damage the heating equipment and blow soot and smoke throughout the building.
  • Leaks on hot water heating systems are never acceptable, anywhere.
    • Leaking pressure/temperature relief valves need immediate attention and repair (Leaking relief valve could be due to water-logged expansion tank, improper control settings (temperature too high), improper automatic water feeder operation (pressure too high), or defective valve (leaky). True, you only have to report the valve.
    • Did you miss problems at the other components?)
    • Corroded relief valves also need to be test by a service technician and repaired or replaced as they may be unsafe and may fail to open when necessary
  • Relief Valves: Do not touch the heating boiler or water heater temperature or pressure relief valve - it may open and fail to shut down. A relief valve which does not work is dangerous since the system is missing an important safety device. Should an over pressure or over temperature condition develop for other reasons, the boiler could explode.
  • Corrosion on heating system parts: Do not pick at corrosion as you may start a catastrophic, un-stoppable leak requiring total system shut-down. Leaks left unrepaired can destroy heating equipment.
  • Tankless coils for making hot water:
    • If there is different water pressure/flow observed in the kitchen in which the hot water pressure is significantly less than cold, even before examining the building's mechanical systems you may speculate that a tankless coil installed may be installed.
    • What other clues suggest that the local water supply may be hard in minerals and that there may be a risk of clogged piping?
    • When the water supply is high in minerals, the hot water pipes or tankless coils clog up before cold water piping. Is a water softener installed? Is there known "hard" water--have mineral deposits clogged the coil?
    • Are there "cleanout" plumbing fittings on the tankless coil piping? Does this suggest a history of clogging and acid-flush treatments?
    • A clogged tankless coil can be repaired or replaced.
    • How severe was that rust you observed at the tankless coil mounting plate? Severe rust may mean that the boiler must be replaced.

Examples of Heating System Defects with Important Implications

...

Technical Reviewers & References

  • Daniel Friedman - principal author/editor of the InspectAPedia® Website
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

HEATING SYSTEMS
HEATING SYSTEM INSPECTION DIAGNOSIS REPAIR

More Information

InspectAPedia.comInspectAPedia ® Home & Site Map
InspectAPedia Blog - News Updates
Air Conditioning & Heat Pumps
Bookstore
Electrical
Environment
Exteriors
Heating
Home Inspection
Insulate Ventilate
Interiors
Mold Inspect/Test
Plumbing Water Septic
Roofing
Structure
Accuracy & Bias Pledge
Contact Us

More Information on Building Diagnostic Inspections and Repairs

  • Carbon Monoxide Gas Toxicity, exposure limits, poisoning symptoms, and inspecting buildings for CO hazards
  • Dust from HVAC? An Investigation of Indoor Dust Debris Blamed on a Heating/Cooling System Reveals Carpet Dust
  • Goodman Furnace High Temperature Plastic Vent HTPV safety recall US CPSC notice
  • Home Heating System Should Be Checked [for proper venting and for CO Carbon Monoxide Hazards - DJF]
  • Inspection Procedures for Oil-Fired Heating Systems Detailed step by step approaches for inspecting complex systems]
  • Lennox Pulse Furnace Safety Inspection/Warranty Program: Carbon Monoxide Warning
  • Oil Tanks - The Oil Storage Tank Information Website: Buried or Above Ground Oil Tank Inspection, Testing, Cleanup, Abandonment of Oil Tanks
  • Oil Tanks Above Ground, UL Standards, guidance for home owners, buyers, and inspectors
  • Plastic Heating Vent Pipe & Other Heating Safety Recall Notices
  • Weil McLain Model GV Gas Boiler/gas valve CPSC recall/repair
  • Domestic and Commercial Oil Burners, Charles H. Burkhardt, McGraw Hill Book Company, New York 3rd Ed 1969.
  • National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
  • The Steam Book, 1984, Training and Education Department, Fluid Handling Division, ITT [probably out of print, possibly available from several home inspection supply companies] Fuel Oil and Oil Heat Magazine, October 1990, offers an update,
  • Principles of Steam Heating, $13.25 includes postage. Fuel oil & Oil Heat Magazine, 389 Passaic Ave., Fairfield, NJ 07004.
  • The Lost Art of Steam Heating, Dan Holohan, 516-579-3046 FAX
  • Principles of Steam Heating, Dan Holohan, technical editor of Fuel Oil and Oil Heat magazine, 389 Passaic Ave., Fairfield, NJ 07004 ($12.+1.25 postage/handling).
  • "Residential Steam Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • "Warm Air Heating Systems". Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals,
  • Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
  • Installation Guide for Residential Hydronic Heating Systems
  • Installation Guide #200, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922
  • The ABC's of Retention Head Oil Burners, National Association of Oil Heat Service Managers, TM 115, National Old Timers' Association of the Energy Industry, PO Box 168, Mineola, NY 11501. (Excellent tips on spotting problems on oil-fired heating equipment. Booklet.)
InspectAPedia.comInspectAPedia® Home & Site Map - Building & Environmental Inspection, Testing, Diagnosis, Repair, & Problem Prevention Advice: In-depth research & advice on diagnosing, testing, correcting, & preventing building defects & indoor environmental hazards. Unbiased information, no conflicts of interest.
GO TO the MOLD and INDOOR ENVIRONMENT INFORMATION CENTER for in-depth advice on avoiding testing for or cleaning up mold and other indoor environmental hazards, odors, gases, contaminants
The Mold Information Center:
What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems
GO TO MOLD TEST KITS: This expert-recommended mold test kit is cheap and yet top performing *IF* you use a competent analysis laboratory!
Use this simple, economical mold test kit
by following our instructions on how to collect and mail mold samples to our lab
GO TO IAQ/MOLD-TEST LAB SERVICES: Mold, Pollen, indoor air quality, field and laboratory services by an expert.Environmental Inspection, Testing, & Diagnosis On-Site IAQ, Gas, Air Testing, Mold Investigation, Sick Building Diagnosis, Lab Services, & Remediation Plan Preparation - indoor air quality testing, problem source determination, supporting lab work, written remediation plan addressing removal of environmental and other hazards and prevention of their recurrence.
GO TO our PRE PURCHASE BUILDING INSPECTION SERVICES: Authoritative information for home buyers and home owners is included with your inspection.
Building Inspection, Problem Diagnosis
, Forensic Investigation & Testing, Repair Consulting

CONTACT Daniel Friedman - Dan is a senior ASHI home inspector, nationally recognized expert on building inspection, building failures, and sick building investigation
Contact Daniel Friedman for website content suggestions or for fee-paid consulting

05/25/2009 - 09/05/2006 - InspectAPedia.com/heat/HeatBoilerDefects.htm - © 2009 - 1988 Copyright Daniel Friedman All Rights Reserved - InspectAPedia® is a Registered U.S. Trademark