American Home Service IAQ Investigation Field Equipment Specifications & SOPs
MoldAPedia ©

Google
 
  • Mold particle count procedures
  • Mold concentration count procedures
  • Forensic microscopy lab SOPs
Our site offers impartial, unbiased advice without conflicts of interest. We will block advertisements which we discover or readers inform us are associated with bad business practices, false-advertising, or junk science. Our contact info is at inspect-ny.com/appointment.htm.

This document summarizes currently popular indoor air quality equipment and sampling devices and reviews methodology for their use, laboratory procedures, and proper calculating procedures to produce particle concentrations and exposure assessments for investigating the indoor environment. More in-depth, un-biased, expert information on these topics and on building defect inspection, diagnosis, & repair can be found at More Information below. © Copyright 2008 Daniel Friedman, All Rights Reserved. Information Accuracy & Un-Biased Reporting are Assured for this website - see pledge link at below-left. New York State License # 16000005303 -- Contents.

IAQ Laboratory SOP(Standard Operating Procedure) Indoor Air Monitoring and Testing Equipment - Particle Sampler Trace calculations recap

Related IAQ Investigation Lab & Field SOP's

  • Trace Calcs recap.doc - this document inspect-ny.com/sickhouse/IAQEquip.htm © 2007 Daniel Friedman - All Rights Reserved
  • For most-recent microscope optical measurements: field width data and calibration see: Olympus-CH-2.xls & Polam Optics.xls
  • Calibration is repeated no less than when an objective is removed/replaced or other microscope optical or stage components are removed/replaced, or if a new technician is employed.

  • For most-recent calculations of % of trace represented by n cross-scans see: Particle Counts.xls
  • For automated calculations of particles or spores per cubic meter of air (spores/M3) from raw airborne particle counts see: @SporeCountWork.xls
  • For spore count worksheets see: sheet 2 of @SporeCountWork.xls

Sampling Device

Trace length

Nom. TraceWidth

Flow Rate in LPM

Pump timer

Calibrated

Sampling Cassettesused with IAQ Sampling Pumps™™™ (Microscope slides, adhesive tape, and other collection media are also used)

Air-O-Cell™ disposable cassette (Zefon)

14.4mm

1.1mm

15
recommended rate

2-10 min. typical

See indiv. Pump device

d50=2.6u

Allergenco D™ disposable cassette (EMS)

14.0mm nominal

1.1 mm nominal

15 lpm recommended, (operates at 5-20 lpm)

1-10 min. typical

d50=1.7u

Cyclex-D™ disposable cassette

Round media

 

20 lpm

2-10 min typical

d50=0.8u

Micro 5™ disposable cassette

Round media

 

5 lpm

5 min. typical

1" tube if using Gilair-5 pump d50=0.8u

25mm MCE filter cassette

25mm MCE filter

Filter area

Various

 

0.45u (F25045)

37mm MCE filter cassette

37mm MCE Filter

Filter area

various

 

0.8u (F37080)

Bi-Air™ disposable cassette

Dual trace 25mm MCE filter

Trace area

3.5 lpm,

10 min grab, 2-4-hr. TWA sample

 

Adhesive tape-clear ™"

Surface particle sampling mold or settled dust/debris

Scotch™ Gloss Finish Multi Task Tape 34-8507-5365-7

Sterile swab

Culture collection

IAQ Air Sampling Pumps and Particle Collection Equipment

Allergenco Mk3™ time lapse slit-impaction sampler

14.5mm, up to 12 traces/slide

1.1mm

15 nom. lpm

1min to 24-hrsmulti-trace

5/17/01
15.1 factory

MK2 d50=0.67

Burkard PAS#1

14.0mm

2.0mm

10 lpm

0-9 min

Factory d50=2.52u

Burkard PAS#2

14.0mm

2.0mm

10 lpm

0-9min

Factory

Intermatic (used with EMS Megalite below)

NA

NA

NA

1 second to
24 hours

Factory

EMS Megalite Pump w/IAQ Options Ser #7038, Mod. 6025SE-V

NA

NA

3-30 lpm

Separate duplex timed receptacle

Factory, pump-mounted rotameter, Lab bubble tube

10/10/05 0 lab

Gil-Air-5-RC pump

NA

NA

1-5 adjustable

1 min to 8-hrs

1/15/04 Lab, Zefon bubble tube (ZBT) + (OD) in field at each use

RadioShack Pump

NA

NA

10 lpm

Manual on-off

Lab 10/10/2003-9/5/2005 (ZBT) in lab & (ZR) in field at each use

Notes: particle collection efficiency d50 for other common devices: (J. Tucker)

AGI-30 liquid impinger ™ 0.31; SAS Slit-to-Agar™0.67; Cyclex impactor 1.80; RCS radial impactor 4.00, Andersen N6 hole impactor 6.61, Rotorod 10.0.

Gas Detection Equipment

Sensidyne Gastec pump (gas detection)

NA

NA

50 or 100 cc/ ™ /full stroke

Manual stroke, manual count indicator

Leak test 11/16/04

8/5/2005

Draeger accuro pump (gas detection) ARUK-FO13 #1-0893171516K09 exp F013 Serial 6400000

NA

NA

100 cc/stroke

Manual, stroke completion indicator, automatic stroke counter

Leak test 11/16/2004

9/5/2005

RTCA Pump#1

Rotary vane vacuum

NA

NA

14.28

11.27 min

Lab 6/11/04total 160.94L

RTCA Pump#2

NA

NA

Tbd

Tbd

Tbd

Other Equipment & Specifications

Tramex

electronic moisture encounter

Delmhorst

twin-point electronic resistance moisture meter

Exergen ™

Infrared scanner ™ surface temperature

OD = flow indicator on device (subject to lab calibration)

ZR = Zefon rotameter, for field use, verified using ZBT in lab

ZBT = Zefon bubble tube (precise), multiple timed events to measure actual LPM

Factory = original calibration provided by factory or independent consultant to factory.

This document supports our General Lab Procedures and Particle Trace Count Procedures.
See www.inspect-ny.com/sickhouse/TraceCalcs.htm

More expert information on this topic

More Information on Indoor Air Quality and Toxic Mold Testing & Building Diagnostic Inspections and Repairs

goto InspectAPedia.com - authoritative, in-depth Building Diagnostic and Repair Information for building buyers, owners, inspectorsInspectAPedia TM Home & Site Map - Building Inspection, Diagnosis, & Repair, Environmental Inspection & Testing - Research Website

GO TO the MOLD and INDOOR ENVIRONMENT INFORMATION CENTER for in-depth advice on avoiding testing for or cleaning up mold and other indoor environmental hazards, odors, gases, contaminantsThe Mold Information Center: What to Do About Mold in Buildings, When and How to Inspect for Mold, Clean Up Mold, or Avoid Mold Problems

GO TO our PRE PURCHASE BUILDING INSPECTION SERVICES: Authoritative information for home buyers and home owners is included with your inspection.Home Inspection Construction Consulting Services & advice for home buyers

GO TO MOLD TEST KITS: This expert-recommended mold test kit is cheap and yet top performing *IF* you use a competent analysis laboratory!Use this simple, economical mold test kit by following our instructions on how to collect and mail mold samples to our lab

GO TO IAQ/MOLD-TEST LAB SERVICES: Mold, Pollen, indoor air quality, field and laboratory services by an expert.Environmental Inspection, Testing, & Diagnosis On-Site IAQ, Gas, Air Testing, Mold Investigation, Sick Building Diagnosis, Lab Services, & Remediation Plan Preparation - indoor air quality testing, problem source determination, supporting lab work, written remediation plan addressing removal of environmental and other hazards and prevention of their recurrence.

CONTACT Daniel Friedman - Dan is a senior ASHI home inspector, nationally recognized expert on building inspection, building failures, and sick building investigationContact Daniel Friedman for website content suggestions or for fee-paid consulting

Google
 

05/20/07 - www.inspect-ny.com/sickhouse/IAQEquip.htm ©Copyright 2006 1995 Daniel Friedman All Rights Reserved